what is difference between differential protection and
distance protection and how we calculate the sloop?
Answer Posted / raju t
Differential Protection:
1. It simultaneously compares the phaser difference & magnitude of the current entering & leaving the protected zone.
2. It works on kirchoff's current law
3. It is a unit protection scheme i.e. it needs current inputs from minimum two different sources.
4. Differential current = |I1+I2| --> Vector sum
5. It cannot be used to provide backup to other relays
6. %Slope = (Id2-Id1)/(Ib2-Ib1)
Distance Protection:
1. It calculates the apparent impedance of a line with the help of voltage & current input connected to the relay. If measured impedance falls below set impedance trip command is issued to clear the fault.
2. It works on impedance measuring principle
3. It is a non-unit protection but can be easily used as an unit protection by co-ordinating distance protection with PLCC
4. Z=V/I
5. It can be set to provide backup to adjoining lines & bus bar depending on the requirement.
| Is This Answer Correct ? | 30 Yes | 0 No |
Post New Answer View All Answers
What are the advantages and disadvantages of negative feed back?
errection check list for transformer maintenance
can anyone show me how the 3 phase power is supplied to socket outlets?
how we can come to know that motor winding resistance which showing by DMM is right or wrong???is there any chart or something that we will compare & check???
Showing results for capital, machinery, stock,wages, carriage in words, salaries, factory rent, repairs, fuel and power, buildings, debtors, sales, purchases, creditors, return outwords, return inwords, drawings, discount allowed, discount receivable, office expenses, bills payable, bills receivable, cash in hand, cash at bank, office rent comes under debit or credit
i have been tasked with a design of protection, metering and control(PMC) relay panel extension to accommodate all PMC relays.There is an already existing panel where this one will be built.What are the design aspects for this kind of project? thank you.
What should be the voltage between Neutral and Ground in secondary side of the step down transformer (230 V to 110 V) with no load condition?
How do i carry out or know the vector group of a Dyn1 and Dyn5 transformer
why the difference arise between HT reading & LT reading (submeters fixed in complexes, apartments etc)if the power factos exceed from 0.9 to 1 can the ht meter reads fast?
234 MVA Generator 3 phase Short circuit current Values required? Gen set Rating-234 MVA, Gen Voltage-18kv, PF;0.8, Xdv:23.5 %, Transformer Rating-18/380KV, 680MVA,Yndd1 two winding, Step up TR, ZT:35.50 %,X/R 4.33 Gen CB Position, CB open ,Disconnected open, Generator Running Voltage 18 Kv, Bi mistakes generator side earth switch Closed during that time short circuit current level in 3 Phase required, and how to test on site 234MVA Generator Short circuit current,
Hello Friends, How can we recognize the CT Star Point is S1 or S2 in case of Electro Mechanical Relays and what is meant by Restraining coil in relays and what is the purpose of that.. thank you in advance..
What is force on parallel conductors ?
What is The Resistance Formula
if two transformers are placed parallel & both have fault impedance of 50KA will it increase or decrease show example?
how to calculate the cable current ratingand and how much of distance the rating will be ok will the distance is incresed what the action we take