Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

how to calibrate the radar transmitter for measuring the
exact tank level if tank is having agitator moving
continiously because due to agitator tank surface level
will vary every time.

Answer Posted / sam

Just increase the damping on the radar's 4 to 20mA output.
This should stabilize the output, even if the local display
still jumps around.
In the DCS there is also damping that will help with the
input from the radar.
You will never be able to measure an "exact" level in a
turbulent application like this so the best you can do is to
use the average over a period of time and that is what the
damping does. It smooths out the ripples in the output by
taking samples of the level measurement and then give a
average output.
Good luck

Is This Answer Correct ?    6 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

how to calibrate electro pneumatic positioner 8013 mil controls ltd ?gsr

7959


Q-Explain the different load conditions that will produced different offset which may or may not be acceptable to thhe control function

2232


how to calculate orifice sizing? and tell me if pipe size bet 50mm t0 200mm then we can use pipe flange??? and above 250mm pipe size should i use D & D/2 Flange? is it right or wrong?

1934


What is eddy current? Describe the operating principle of proximity probe.

2375


WHAT IS THE DIFF. BETWEEN SKIN TEMPERATURE AND PASSES TEMPERATURE..?

2576


when the instrument tapping on pipe line is located below and transmitter is located above the tapping point for liquid service transmitter, what should we do, is there any additional drain valve is required??

2227


I need to know steps to Calibration Valve Guard......

1526


what is isloted barrier how it works and what are the main purpose.how it make safe area.

2185


What is force balance principle?

1224


what is difference between HOT permit and cold permit

2283


How to calibrate an pressure gauge with yantrika test bench?

2945


What is the GK Value in Flowmeter?

3767


I was working on calibrating turbidity transmitters endress+hauser at effluent polishing plant.We calibrated using NTU buffers.What happened is that when we immersed the sensor, everytime we raise and lower the sensor gradually, the reading will vary.my question is that is there any specifications on what is the required distance from the bottom of the container with buffer to the face of the sensor?Is it ok to install the sensor in a medium which has turbulence specially if bubbles are present?

2251


What is frequency factor in massflow meter? When using frequency output?

1912


centrifugal compressor interlock? Tell me the parameter at which compressor will trip

3233