Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

how to calibrate the radar transmitter for measuring the
exact tank level if tank is having agitator moving
continiously because due to agitator tank surface level
will vary every time.

Answer Posted / sam

Just increase the damping on the radar's 4 to 20mA output.
This should stabilize the output, even if the local display
still jumps around.
In the DCS there is also damping that will help with the
input from the radar.
You will never be able to measure an "exact" level in a
turbulent application like this so the best you can do is to
use the average over a period of time and that is what the
damping does. It smooths out the ripples in the output by
taking samples of the level measurement and then give a
average output.
Good luck

Is This Answer Correct ?    6 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

WHY THE DEGREE OF VALVE PLUG AND VALVE SEAT IS SLIGTLY DIFFERENT I CONTROL VALVE TRIM DESIGN

1930


Explain Gas Turbine startup and shutdown sequences

4258


what is the procedure of O2 sensor(ABB) calibration?

2130


How can a d.p. Transmitter be calibrated?

1211


how do i tune dearator pr control valve using PID. we set the set point is 0.6kg/cm2 now i want 0.5 to 0.7kg/cm2 limits so what should i give p,i,d values. then pls explain how do set pid values for control valve tuning?

1849


what is intrinscily safe system and where we use?

2431


Please send me the sample question of Instrumentation of hpcl/iocl exam. my mail id hihi_kiholo@rediffmail.com

3163


detail of mass flow meter pricipal

2263


What is Positive Calibration and Negative Calibration?

2176


Hi i m B.E. In elect. & comm. I m workin in bio mass plant from 6 mnths as inst. Engg. but now i m in dept. Of operation as shift engg...which is best operation or inst. 4 me? M confusd..plz help and reply me..

4128


send me HPCL paper

10011


how to work static pressure sensore how to work dpt

1814


flow transmeter accuracy 0.075% of full scale & find ucertainty is 0.025 % so what is maximum limit band of uncertainty

2254


What is difference between ESD and PLC please Explain me clearly.

4825


what should he know if he is an assitent engineer instrumentation in cement industries of experience of 10 - 15 year.

2041