Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

how to calibrate the radar transmitter for measuring the
exact tank level if tank is having agitator moving
continiously because due to agitator tank surface level
will vary every time.

Answer Posted / sam

Just increase the damping on the radar's 4 to 20mA output.
This should stabilize the output, even if the local display
still jumps around.
In the DCS there is also damping that will help with the
input from the radar.
You will never be able to measure an "exact" level in a
turbulent application like this so the best you can do is to
use the average over a period of time and that is what the
damping does. It smooths out the ripples in the output by
taking samples of the level measurement and then give a
average output.
Good luck

Is This Answer Correct ?    6 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

What is the purpose of LO Overhead tank in turbines.

1989


In VVVF DRIVES VOLTAGE IS ALSO VARY WITH THE FREQUENCY. HOW? WHAT IS THE DIRECT FORMULA RELATING THESE TWO.

2344


Describe a time when you anticipated potential problems and developed preventive measures.

2894


Explain about the leakage class of the control valves

1981


i need some objective type questions in instrumentation

4887


what do u mean by compensation n pid tunning?in pid tunning what you tunned?is it possible 2 tune p i d

5349


how to calibrate Necleuonic level transmitter.?

2091


How to Calibrate Ultrasonic flow Transmitter in Field

1247


components of control circuit belongs to control valve

1638


Using your own examples solve a problem involving normal table. (experimental method and analysis)

1134


Hi Friends i need Electronics&Instrumentation Engg question papers for BARC written test by coming 20th May 2008 pls post ur use full info to kkumarei@gmail.com. Or for suggestions pls give one missed call to 9962122264

1938


what is installation and commissioning of (fat & sat) of power plant dcs ? this question keeps in desirable conditions of one company .

4831


how will you segregate the alarm levels in alarm management system during factory Acceptance Test

2370


how u calibrate pneumatic n motorized c/v?

1952


Calibration of controller (pneumatic)

1952