Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

how vector surge relay works ?

Answer Posted / birendra singh mehra

Vector shift and ROCOF are basically the same. It is a
function that will disconnect the generator from the grid
in case the grid disappears (black out of the grid/ loss of
mains/ mains failure).

Vector shift and ROCOF are basically the same. It is a
function that will disconnect the generator from the grid
in case the grid disappears (black out of the grid/ loss of
mains/ mains failure).
This function is necessary because in case the grid
returns, it is likely that the generator will not be
running synchronously with it anymore. Thus this would
cause a short circuit.
This type of protection is called either Rate of change of
Frequency (ROCOF or df/dt) or vector shift/ vector surge.
The only difference is the way the set point is expressed.
ROCOF type is used in UK while the rest of Europe usually
uses vector shift.
ROCOF Relay
This relay will trip the generator in case the frequency
changes more than a certain set point within a certain
amount of time. Thus the adjustment is done in Hz per
second [Hz/s] (if the frequency changes more that XHz per
second the relay will trip). The frequency change appears
because the load situation on the generator will change
suddenly in case the grid is lost. This load change causes
a change in the engine speed which is equal to a frequency
change.
Function principle of the ROCOF Relay:
Practically the ROCOF relay will detect zero crossings of
the generator voltage. It measures the time between the
zero crossings and calculates a new frequency after each
zero crossing. In case the frequency changes too much since
the last zero crossing, the relay will trip.
Vector Shift Relay
This relay will trip the breaker in case it detects a phase
shift in the generator voltage. For example if a zero
crossing occurs some degrees earlier or later than
expected. Thus the adjustment is done in degrees.
The vector shift is again depending on the change of the
generator frequency. In case the grid is lost, this will
result in a sudden change of the generator frequency. A
change in frequency will move the zero crossing of the
generator voltage earlier (in case the generator load has
dropped) or later (in case the generator load has
increased). This shift is expressed in degrees. If this
vector shift is larger than a certain set point the relay
will trip.
Function principle of the Vector Shift Relay:
As you can see from above the Vector Shift relay will also
detect zero crossings of the generator voltage. It compares
the calculated zero crossing from the previous periods with
the latest zero crossing. If the difference is larger than
the set point, the relay trips.
Conclusion 1
As you can see from the function principles of both relays,
they are actually the same. Both relays rely on detections
of zero crossings of the generator voltage. The only
difference is the way how the trip level is expressed.
The utility companies require certain trip levels (just as
marine classification societies). In the UK they request
this in Hz per second, in the rest of Europe in degrees.
This goes so far that one of our customers in Switzerland
who used a T3500 ROCOF relay was forced to buy an
additional Vector Shift Relay in order to meet the utility
companies’ requirements (so they could adjust it in
degrees, not in Hz/s).
Conclusion 2
You can see from above that both relays require a sudden
load change of the generator in order to detect the loss of
the grid (mains failure). In case the generator would be
running parallel with the grid but only supplying as much
power as is used by the local consumers, a loss of grid
would not result in a load change on the generator. The
frequency would not change and thus neither the ROCOF nor
the Vector Shift Relay could detect this.
Therefore the utility companies require a minimum import or
a minimum export in case a generator is to run in parallel
with the grid.
Rate of change of frequency relay (ROCOF)

Is This Answer Correct ?    78 Yes 9 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

What is the disadvantage in proportional controller?

1154


How to measure the Harmonic Distortion of UPS ie THD?

2340


how we decide scurt (disc) of insulator with respect to kv rating

3567


what is the difference between surge protection capacitor and surge arrestor

2319


State the other types of Air Conditioners?

2056


what does a k rating in a transformer means?

2501


Dear sir my name Ankit i m Diploma holder present working in Welspun Corp ltd Anjar as Asst.engg (salary 14400/month ctc) i Would like to change my company also i have selected in ford India pvt ltd Sanand as trainee Tech with salary 12000/month so please suggest me for changing my job hope for *ve response

2914


how to determine Sq.mm size of finolex power cables.

2001


what is size of 3phase 4wire cable to be used for 11 ton ductable A.C and how to calculate cable size for different load

4020


Why space heater is required for each verical bus bar chamber? if one space heater is adequate or not for anti condensation?

2528


Can you used moeller lzm1 mccb in a dc system with 125vdc and 20ka short circuit current , beside is it have 24 or 48 volt shunt ? Beside how long current can through from An MCB shunt contacts? (like Z7-AS 24 V)?

2085


hi,every one, i have to write the search paper on "performance policy optimization" of NGN (next generation networks). i need the material on this topic. can any body help me. please tell me any useful site where the good material is available and name of any reference book. it should be a great help for me.

1923


In between UPS out going changer over switch and ups raising main input, both side cable gland producing heat but the cable doesn't get heat,Why?

2262


how can maintaince the acb contactor moveing and fixing kit

2071


what is a bus riser in power system and why it is used

46199