What will happen to the speed of synchronous machine
subjected beyond the pull out torque?
Are the behavior shown by rotor remains same for both the
alternator and motor?
Answer Posted / iamdon
Beyond pull out torque, the speed of synchronous machine
changes from synchronous speed.This is called LOSS OF
SYNCHRONISM or PULLING OUT OF SPEP.
The behaviour shown by the rotor of synchronous machine in
this condition will NOT REMAIN SAME for alternator and
motor as expalined below.
Motor:An increase in the SHAFT LOAD TORQUE beyond the pull
out torque will cause the rotor to lose synchronism and
thus to SLOW DOWN.
Generator:An increse in PRIME MOVER TORQUE beyond the pull
out torque will cause the rotor to lose synchronism and
thus to SPEED UP.
Author:arbelectbit@yahoo.com
| Is This Answer Correct ? | 2 Yes | 0 No |
Post New Answer View All Answers
why steady state stability limit is greater than transient stability limit ? How it can be explained ?
What is the Temperature to be set in Thermostat provided in Marshalling box of the Transformer / Motor.
in power generator normaly voltagr betwween esth to neutral is 0 but my work place generator show the volatge is 60v any body know why? thanks
What is Servo Ventilated Motor?
Explain what is electric traction? Explain few advantages of electric traction system?
what is spadar bar .why I use in DC generator.
What will happen if we on 200kvr capacitor bank(11kv in bus)If there is low load on transformer (1.5 mva 33/11 kv)
1.how many types of relays? 2.difference between ATS& STS?
what are the different sizes of U.G. cable & where these cabl;es are used according to voltage ..
lenz law application and define
what happen when power factor of 2 parallely operated transformer become equle?
determine two methods to find loose connection in operational electrical system?
PLEASE SEND THE PREVIOUS YEARS QUESTION PAPERS OF RRB JUNIOR ENGINEER-ELECTRICAL
On a 6 KVA UPS we have to provide a DC MCB for Battery bank of 16 nos (12 V 42 AH). What Shall be the current rating of DC MCB ?
How can I model an open-delta ground transformer for a network supplied by 4 unit GTG and power transformer in ETAP?