Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

Can a transformer designed for a particular voltage and
frequency rating be used for different set of mentioned
ratings? Assume that the winding does not get burnt because
of overheating at higher voltage.
If yes, then under which constraint it is possible?

Answer Posted / iamdon

Yes.

A transformer designed for a particular voltage and
frequency rating can be used for different set of
mentioned ratings as long as ratio of voltage to the
frequency does not deviates from designed value.
By emposing this constraint, the core of the transformer
will not saturate.Since the winding is assumed capable of
sustaining overheat, so only deciding factor is V/f ratio.

i.e,(V/f)=fixed at rated value.
50 Hz at 500V
25 Hz at 250V
75 Hz at 750V and so on.

Author:arbelectbit@yahoo.com

Is This Answer Correct ?    8 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

how to Select Lighting arrester? What r the parameters to be considered for the selection of Lighting arrester ?

1675


What is the estimated total hydropower potential of india?

1085


How does cost of generation from hydropower plant compare with other sources of electricity?

994


state the working of discharge lamp?

1948


How to do stting of vl250 siemens MCCB

2887


i am going to correct power factor of 1600kw induction motor,when i calculate capacitance of capacitor it is three time more in star connection than delta. if motor is star connected which connection i shall adopt for capacitors and reason for adopt this connection

1793


what is dry and wet frequency withstand voltage? why & where it is used??

2353


what is the calculation method to design core and winding of a 200kva 3phase distribution transformer?

2343


how to ctrl motor by use of ac or dc drive.plz explain evdintly

1966


Define cuttoff frequency?

1020


234 MVA Generator 3 phase Short circuit current Values required? Gen set Rating-234 MVA, Gen Voltage-18kv, PF;0.8, Xdv:23.5 %, Transformer Rating-18/380KV, 680MVA,Yndd1 two winding, Step up TR, ZT:35.50 %,X/R 4.33 Gen CB Position, CB open ,Disconnected open, Generator Running Voltage 18 Kv, Bi mistakes generator side earth switch Closed during that time short circuit current level in 3 Phase required, and how to test on site 234MVA Generator Short circuit current,

2171


The SFC of an engine is 0.25 kg/kW hr. when the fuel used has a calorific value of 36000 kJ/kg. the thermal efficiency of the engine is

1887


Why an ac solenoid valve attract the plunger even though we interchanges the terminal? Will the poles changes?

1153


details of oil cell size of Breakdown voltage test of tranformer oil details as per Standardswith mushroom electrodes?

1826


should %impedance be high or low in a power transformer? if so why?

1860