Answer Posted / me
Greetings all,
iam working in an out door lighting design for our plant
and i calculated the total watt needed (sum of all lights)
= 53 kw, 220 volt
our power supply is 480V
so, I chosed a 75 KVA transformer dry type 480/220-127 V 3
phase 60 Hz
cable size from feeder to transformer primary = 50 mm2 (1/0
AWG)
cable size from transformer secondary to distribution panel
board = 125 mm2 (250 MCM)
distribution panel board main breacker = 250 A
So, are my calculations ok ? any changes or suggestions ?
thanks in advance
Is This Answer Correct ? | 2 Yes | 0 No |
Post New Answer View All Answers
hello!my name is sheikh iam preparing for indian engineering servieces,please send me the old question papers..to sheikhshaazforjobs@gmail.com
sugest any typical project ?
Explain about 3 phase motor fault current calculation with examples?
can anyone explain 11kV 3core cable megger,hi pot test procedure with connection details?
before synchronizing an alternator,power factor is leading ,why?
Which motor is 3.3 or 11kV more reliable, in terms of efficeancy,maintenance, reliability.
what do you mean by plant earthing system.
For high frequency application we use which transformer?
Can we use a absolute encoder to show rpm of a motor ? what about the condition when power is off ? what is difference if a incremental one is used ?abanirout@gmail.com
What Should be the value of Vector Surge angle at Tripping and how to calculate it?
ACB & VCB how do work and saftes and how can maintenance in this and parts name show with picture
Give details of your interested designation, the post you are interested to serve the company better and explain why you think you can serve the company better in such position if employed?
Make a list observation on Transformer?
why does connected a indutor with mnsformeretering core of current transformer ?
how to compare with Relay settings for HT< panels, RMU panel, and PSS CSS transformer?? 1) Load amps, 2)Tripping time, 3) CT ratio, 4)Cable size 5) Transformer KVA rating 6) transformer full load amps