Why ACB is used in LT why not in HT and why VCB is used in
HT why not in LT
Answer Posted / iamdon
In ACB(Air Circuit Breaker) arc extinguishing and
insulating is carried out in air medium where as in VCB
(Vaccum Circuit Breaker)it is carried out in low vaccum.
At high voltages, air inonises and losses its dieectric
properties which makes the ACB unsuitable at HT.Thats why
ACB is used at LT not at HT.
Vaccum can suastain high voltage(not ionises) and does not
losses its dielectric properties which makes the VCB
suitable for HT.
Since VCB is costlier and require more maintenance as
compared to ACB.So VCB is not employed for LT where cheaper
option as ACB is available.
Author:arbelectbit@yahoo.com
| Is This Answer Correct ? | 43 Yes | 3 No |
Post New Answer View All Answers
what is ATS & RING MAIN UNIT in Distribution System?And its Function.
what happens when dc generator coupled with cycle shaft.also explain what happens when its loaded
What is evaporator & condencer & compressor
i need project topics along with circuit diagram in the electrical and electronics engg and also some websites regarding projets.
WHAT IS VCB SAFETY
what is meant by IGBT how they differ from tyristor ?
Is there possible to Test Transformer for Overfluxing Capability. Or is there any firm who does Overfluxing Test on Transformer?
What is a feedback in control system?
What is relation between mu(nought) and epsilon(nought)?
What are the classifications of heating element?
In the ACB breaker capacity is 2000Amp but this each phase taken 1250 But total beldibg load is 600amp or 700amp watt is the problem
what is the difference between megger and earth resister ??
Define unilateral circuit?
Define norton equivalent circuit?
If we need 4c× 50mm sq cable but it's not available so we can pull 4c×25mm sq two cables?