why the CT ratio secondary is always divided by 5 for eg(
75/5,80/5,50/5)
Answer Posted / iamdon
CT is used mainly for Instrumentation(Measurement and
protection system) purposes thats why it is also termed as
instrument transformer.The measuring and protecting devices
are not rated to sustain high currents.What a CT does is,
it lowers the current in secondary side so that measurement
as well protection can be done at a reduced level of
current.
The digit in CT ratio of secondary side is IS standard for
rated secondary current so that uniformity among manufactures
be established.
The various values of secondary currents are
1)in the range of 0-5 amp e.g, 1A,5A
2)in the order of mA(particularly 40mA)in case of digital
devices for measurements and protection.
Perhaps Shayam had ingnored this fact.It cann't be any
number.
Author:arbelectbit@yahoo.com
| Is This Answer Correct ? | 15 Yes | 2 No |
Post New Answer View All Answers
There is any especial requirement for motor to drive through with VFD?
what is the formula to calculate voltage drop/loss on 66KV Transmission Line?
What is nichols chart?
What is Load sharing of Transformer ?
what is the clear formula to calculate cable size for a load
Write down the name of 2 lady Bir Pratin of Bangladesh
Can i replace Earth leakage relay to the faulty Earth Faulty Relay
What is the formula to calculate the size of Aluminium and copper cable?
battery capacity use of made?
What are the types of class b amplifier?
In a 3 phase 4-wire system. For a 3.5 core cable if all loads are single phase and balanced, what will be neutral current? will it be sum of all phase currents? Or it will be zero? And if loads are unbalanced what will be neutral current?
What is a parabolic signal?
Give details of your interested designation, the post you are interested to serve the company better and explain why you think you can serve the company better in such position if employed?
What is marx circuit?
how we calculate torque ? how we improve it ?where torque will either motor or generator ?