Answer Posted / prasun bhaumik
First put normal PT supply and then increase the current up
to the pick up level and then upto 2 times of it then see
the time of operation.
Then keep the current at plug setting value , now decrease
the voltage gradually to see the minimum restraining
voltage at which the relay will start to operate