Answer Posted / tareq harb
There are 3 types of excitation systems:
AREP, PMG & Self excitation.
in self excitation the AVR (Automatic Voltage Regulator)
takes its power directly from the out put terminals of the
generator, the main disadvantage of this method is that
when the generator output volatage drops the feeding to AVR
will be insufficient. suppose SHORT CKT fault takes place
on generator terminals as a result the output voltage will
drop too much & AVR shuts down directly with out feeding
this short CKT, if running on island mode (load sharing
mode) the hole system will trip.
But in PMG excitation system, PMG will feed AVR with the
same power nevertheless out put volatge, in case of short
ckt PMG alternator can supply 3 times its rated current for
10 seconds giving enough time for generator breaker to trip
eliminating the short ckt with out affecting the system.
as we see the main advange of PMG ALTERNATORS is its
enhanced immunity against short ckts.
Self excited systems is preferable in single mode operation
as it is cheaper & shorter prime movers.
PMG is strongly recommended in island mode operation.
Is This Answer Correct ? | 23 Yes | 0 No |
Post New Answer View All Answers
what do w do when the output of generator is fluctuating?
why ups rating in kva? and why ups are in parellel?.why isolation transformer is used in ups?
WHAT IS MOBILE SUB-STATION? & REALLY BENEFIT IN INDIA
working principle of AC Servo Motor with its construction
Is it required to lay 2 runs of GI wires along with armoured cables from one power DB to another Power DB?
Why neutral cable carry current.
How the frame size of a flange mounted AC induction motor is calculated?
What is the exact formula for one weber of magnetic flux?
WHAT IS MEANT BY INSULATION CLEARANCE IN VACCUM?
How is operate breaker failure scheme in substation
what is through fault?
In Power cable specification what is U0/U and Um.
HELLO SIR, IAM PREPARING HPCL EXAMS. SO PLS SEND MATERIAL OF HPCL ELECTRICAL ENG..TO VIJAY_8888@YMAIL.COM
why ct ,cvt should be stored in a vertical position?
What are the advantages & disadvantages of a group electrive drive?