how to calculate no. of earthing pits and their diamensions?
no. of lightning arrester rods which are required to
protect a building of 35 mtr and we calculate?

Answer Posted / william lobo

The number of earthing pits depends on the soil resistance.
We may require earth resistance of 1ohm or 3 ohms at the
most. To get this we will have to install at least 2 pits
and as per parallel formula i.e. 1/r1+1/r2+1/r3= 1/R. We
have to keep on increasing the number of earth pits till we
get the required value for R=1 or 3 as per requirement.

Is This Answer Correct ?    14 Yes 6 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

how is the connection of a 3 phase ct trivector meter done on a pole mounted transformer

899


there is an alternator 480 k.w, 400v,50hz, 4-wire running on load having leakage alternator body earthed current 38 A. is it within acceptable limit? if yes then give reference if no then how to bring within specified limit

1472


sir i had plane to do some project with the base of hopkinson test in AC supply its possible

1348


Sir, I have applied for the of Assistant.engineer of NPDCL. please send me all AP TRANSCO AND JENCO solved papers of previous exams . I requested send me the papers to my id as soon as possible (rajanikanth_peddi@yahoo.co.in) (This is very urgent) Thank You,

2383


Define what is the function of anti-pumping in circuit breaker?

675






As a electrical engineer.. what are the basic norms should follow in transformer oil testing.. 1.What is the Electrode type? 2.How long time you will give for oil testing?

3077


A commercial Building is designed with 14th floor levels with indoor substation of three phase transformer with rated capacity of 1000 Kva.The transformer delivered 65% of its rated capacity at 0.67 power factor lagging.Because of low power factor, the power customer was penalized and certain cost was charged accordingly based on every point percentage lower than 85%.This situation may repeatedly happen on the succeding energy bills of power customer.The power customer is desired to improve its historical power factor of 0.67 lagging and no further penalty be impose by the local power company on the next bill. Q: Identify the appropriate solution you want to offer to Client?.Justify SCIENTIFICALLY and MATHEMATICALLY the principles behind the solution.

1329


Please tell me in DETAIL about the following 3 types of fuses or recommend me a good power system protection book or a website link ? 1.Dropout Fuse 2.Striker Fuse 3.Empulsive fuse (not sure if its impulsive or explosion fuse , sorry)

1662


critically criticize the application of ring main unit in power system

984


can we use CBCT in neutral of solidly grounded transformer? in place of three phases we can pass only one phase which decreases the size of CBCT?

1751


How to calculate fault level of 11 KV system

1499


Is there a standard depth of gravel fill in Substation Switchyard? Please give a design/drawing. Thank you.

4797


How we calculat the NGR of 3phase Generator, Our generation voltage 11KV

2866


What is different between resistance grounding system and resistance earthing system?

665


Which type of motor is used in trains, what is the rating of supply used explain working principal?

763