Hai I have 2500KVA,Transformer,13.8KV/380.DELTA/STAR.How
much load that I can take interms of current?How can I
calculate also when I have loads in KW?
Answer Posted / saqib haroon
as per my point of view,answer of the input current is
wrong. Why the respectable brother put power factore value
with KVA rating, as per formula only once we will put PF
value, which will divide this KVA rating.
In this case the answer will be
P1= 1.73*V1*I1*cosphi
2500= 1.73*13.8*I1*0.8
2500/1.73*13.8*0.8= I1
131 A = I1
Remaining portion is OK
| Is This Answer Correct ? | 3 Yes | 5 No |
Post New Answer View All Answers
What happened ,If 3 phase clearance not maintained in 33KV Line,11KV LIne etc?
Why are lt windings placed near the core?
how to select size of hardware for linking aluminium busbar is it depend on area of busbar or current flowing through bus bar
what is the min and max ohmic resistance for the earthing rod installed for lighting poles for street light network
what is the ms flat constant for calculating earth mat design calculation?
with 3 phase board on a 63 amp rcd is it ok to have 6 electrical showers 2 on each phase and what problems could happen
Why Water motor is not taking a load or pressure while everything is correct. (Note: Motor running properly)
what is the thumb rule for determination resistance of resistor?
1) Explain why we don't link the two earthing system ht and mv on a pole mounted transformer sub-station.
If Polarization index of motor 8.75 at 500volts of medium voltage 4.16 KV motor what this mean winding good or bad pl answer if any reffrence book give me the link
What is meant by Load Encroachment in OHL Feeder Protection?
what is the meaning of impedance protected in instrument cooling fan
What are conduct on the testing in cf in ur site?
Why open circuit test of transformers is conducted at rated voltage??Why not any other voltage??
How to calculate cable size by using load.?? Any formula...