Answer Posted / ramji
Mr.Sudheer u r not clear.U r telling the condition after DG
starting only, not during running.
Mr.Shri can u please explain me how the voltage will be
fluctuating if the AVR is OFF.
In parallel mode if the AVR of the suspected DG
fails, then the reactive power of the particulat DG gets
reversed because the DG will be out of its running
quadrant.Since the reactive power is reversed, DG will be
trip on under reactance.Also if it is not tripped, its
outgoing current will be increased, so it will trip on Over
current.
In island mode if the AVR of suspected DG set
fails, then the loads connected to it will be thrown off
immediatly and the DG may trip on prime mover overspeed due
to sudden throw of load or undervoltage protection on DG.
| Is This Answer Correct ? | 6 Yes | 2 No |
Post New Answer View All Answers
What information we need to prepare relay coordination chart
i want to know that what is the eligibility critaria for ongc exam?
how to remover corona effect and hysteresis losses from contactor
Why is it prefer to initiate circuit breaker failure by "86" lockout relay not by "94" tripping relay ?!
i am an maintenance engineer. one distribution board have 5 feeder. recently its ELR trips frequently, but it take some times after trip( 10min,20min..)but 3 feeder no load. two feeder only loaded. i checked one feeder IR value all values are above 50Mohm.but B phase to Earth is only 9Mohm.any problem about low value
How does the phase sequence controller works, how it identifies the phases? confirm working principle
11kv/433v delta/star distribution transformer primary side full load Ht current is 83.33A in , but input side VCB rating 800A.why?
WHAT IS VCB SAFETY
if the number of poles generated in stator and rotor side of an induction motor are different then what will happen and why?
How to confirm the Phase shifting Transformer VECTOR GROUP relation , as below ZNy11.45d10.45-ZNYy0.15d11.15
we have provided 30 nos. relay contacts in panel.I want to know how do we do the numbering for the relay contacts as per any applicable standards
witch pump used in wtp
What is the function of probe in cro?
What is the formuala to calculate the rating of motor protection circuit breaker
Why derivative controller is not used in control systems?