Answer Posted / ramji
Mr.Sudheer u r not clear.U r telling the condition after DG
starting only, not during running.
Mr.Shri can u please explain me how the voltage will be
fluctuating if the AVR is OFF.
In parallel mode if the AVR of the suspected DG
fails, then the reactive power of the particulat DG gets
reversed because the DG will be out of its running
quadrant.Since the reactive power is reversed, DG will be
trip on under reactance.Also if it is not tripped, its
outgoing current will be increased, so it will trip on Over
current.
In island mode if the AVR of suspected DG set
fails, then the loads connected to it will be thrown off
immediatly and the DG may trip on prime mover overspeed due
to sudden throw of load or undervoltage protection on DG.
| Is This Answer Correct ? | 6 Yes | 2 No |
Post New Answer View All Answers
what is Fan Control Cubicle
What are the difference between CT/PT operated Meter and RRAMR Meter for HT/LT application?
how to define tell me about self
which pump used in STP
Readings of ER300P Trivector meter
i need project topics along with circuit diagram in the electrical and electronics engg and also some websites regarding projets.
Explain different types of d.c motors? Give their applications
What is the difference IN MCCB's between thermal magnetic and electronic tripping system ?
Why derating factor os applied on Cables?
What is VSCF windelectrical system?
What do you mean by turns ratio of instrument transformer?
how define the torque in ac drive. from electrical side in the drive friquency ,voltage and current three factor is there.
What is the reason of polyphase induction motor tripping suddenly on high current during running at 70% laod? Motor IR , winding resistance & inductance balance. Motor no load current is balance and ok as per mgfr. data.
what is the operating time for LBB and how does the LBB relay realise whether cb is opened or not?
Why a Permanent Magnet Generator has higher frequency as compared to frequency of main alternator?