I have connected 04nos. earthings to a transformer through
04nos. earthing pits seperately. 02nos. earthings are
connected to T/F body, and 02nos. earthings are connected to
T/F neutral.T/F capacity is 2000KVA, 11KV/415V. But after
completing of 02 years successful operation ,we are
facing following problems-
1. CT/PT occured blast one time
2. HT cable box occured blast two times
3. One body earthing strip and one neutral earthing strip of
transformer are overlapping at some places. Whenever these
two strips are pressed at overlapped points, they made spark.
What is the reason of spark?
Please explain the reason & rectification of above problems
Answer Posted / ullas
the answer follows.
1. ct/pt unit blast doesn't relate with the problem. it may
due to its poor quality , or some other reasons.
2. ht cable end box blast can be occured in so many ways.
may be due to rain water entered in to the end box leading
to short circuit the phases.
or due to poor quality,etc maybe the reason.
you can do one thing.
please disconnect the earthing of ht cable armour either at
transformer side or at the double pole structure.
3. this sparking indicated that your transformer neutral is
no longer maintains zero potential.
so please first measure the voltage of neutral.
this is done by inserting a spike five meters from the
transformer and take this terminal as earth terminal of
zero potential. and between this terminal and transformer
neutral measure the voltage developed.
if it is indicating a sufficient voltage, then it is true
that your neutral is shifted from its zero position.
if there is any fuse used in the neutral circuit, change
it in to a link.
check the whole circuit for any abnormal conditions.
| Is This Answer Correct ? | 1 Yes | 0 No |
Post New Answer View All Answers
What is fault clearing time for Current Limiting Moulded Case Circuit Breaker?.
define digital electronic
Why AC & DC capacitor are use in UPS ??????????????????
Can we indroduce the principle of single phase induction mator to Transformer? i.e. by Producing rotating flux in the transformer.
by what factor the starting current is used when comparing star and delta connection for motor starting?
i have gear oil pump with single phase motor.some time its motor starts running in reverse direction rather than forward direction...whats the reason behind this issue. 1- either capacitor is week? 2- or winding is week?
If breaker is undefined position, first step to do.
Igfet is a
How is the gain affected by the introduction of feedback in a control system.
are there rmu for 3 transformer?
what is servo motor and how to work it.
how to test the turn ratio of 3 phase transformer using volt meter shoe the curcit diagram.
I WANT HOW CALCULATE TO CABLE FOR WELDING PLANT ?
How can we calculate strength of copper hich is supplying electric power to heater and in it hold the heater also and what r all types of forces which is acting on it...
Why 9KV surge arrester having 7.65KV of MCOV?