Two CTs 1600/1 and 35/1 are in series. while checking the
ratio test of a CT(1600/1),same 1600A will also pass
through the CT having ratio 35/1.
Will it be harmfull to the ct(35/1),if yes , what will
happen.CT secondary is shorted
Answer Posted / ullas
if 1600 ampere current is passed through the second ct
having turn ratio 35/1 the definitely it will be
damaged.,since the ratio test equipment takes few seconds
to indicate the ratio error the condition will be worst .
no doubt.
each ct have certain burden value indicated on it as 10va,
15 va etc.
consider the case of 35/1 ct. hhaving burden 10VA.
this means while 35A is passing through the primary 1A is
produced in the secondary. and and this current can create
a potential up to 10V.
then calculate the value of secondary current curresponts
to 1600A primary current.
the primary of 35/1 ct is not designed to meet 1600A. so it
shall be burn out.
if we keep the two cts as series connected and 35/1 cts
secondary shorted. then also primary winding of the 35/1 ct
will not withstand with the 1600A.( it will simply act as a
conductor because there is no secondary.
Is This Answer Correct ? | 4 Yes | 1 No |
Post New Answer View All Answers
What is meant by RVT and NDR ? expansion and details of it
which type of motor is used in automatic swing gate
How to Calculate The Neutral Earth flat design calculation for the Synchronised generator (Gen 1-650Kva, Gen 2-725Kva
sir am giving jspl exam on 19th oct . i belong to eee, so plz send previous question papers ..........to dis id abhilash203@gmail.com
hi, in the event earth grounding is not available in a project, is there any other way to make the elcb work? fyi, i have an instant water heater (6.5kw) installed, however if there is grounding in the heating element inside the heater assembly, i will get grounded. thank you in advance to those who will answer my question.
Why earthing is necessary for any equipment?
How can we design a HVAC Plant room which includes AHU,FCU,Chillers,Cooling towers, Pumps etc & how will they work? any Drawing if possible?
Please provided formula for calculate the cable size from step up transformer to M.V panel, run overhead aluminum cables, total load is 5mega watt, total length 900 feet.
i had aplied Hindustan Petroleum corporation limited for the post of maintenance technician -Electrical,i want model questions,if anybody have please send it or please advice?
When and where resistance earthing is used ? How to calculate the time constant for earth fault
What is the effect on 3phase induction motor if current setting knob of DOL kept at minimum current?
Dear sir, I completed DECE In the year 1995.Now i am working in a private company from last 10 years as an Electrical supervisor.The company having a 1000 KVA transformer.Now i try to apply "C" Licence. I am eligible or not.If not eligible,pls give solution.
Classify milling machines.
specific difference of ICT&Auto Transformer
what is the standard duration after failure EB power