I have connected 04nos. earthings to a transformer through
04nos. earthing pits seperately. 02nos. earthings are
connected to T/F body, and 02nos. earthings are connected to
T/F neutral.T/F capacity is 2000KVA, 11KV/415V. But after
completing of 02 years successful operation ,we are
facing following problems-
1. CT/PT occured blast one time
2. HT cable box occured blast two times
3. One body earthing strip and one neutral earthing strip of
transformer are overlapping at some places. Whenever these
two strips are pressed at overlapped points, they made spark.
What is the reason of spark?
Please explain the reason & rectification of above problems
Answer Posted / k.bhaskar
I think your neutral earth pits resistance is not
good,ensure each earth pit resistance with out grid.The
reason for sparking may be body earth is good and some
potential is there in the neutral path.
Second ensure transformer core channel to earth connection
(inside).Measure the winding resistance and unbalance load
distribution may also cause developing voltage in Neutral.
| Is This Answer Correct ? | 2 Yes | 0 No |
Post New Answer View All Answers
Explain in details how you would react to an unexpected incident when your supervisor or manager is not around to give instructions?
how can tell us the AC indoor or outdoor which Tr and formulls
Why space heater is required for each verical bus bar chamber? if one space heater is adequate or not for anti condensation?
how to maintain frenquncy with syncronising sub-station for distribution
I have motor 1500 HP and , 4160 V , 60 HZ , then i need the rating of transformer which can feed that motor ??
(1)The demand for electricity , the amount of renewable generation available, the amount of fossil fuel generation available and the cost of the fossil fuel generation are shown in table below period(hrs) demand(MW) renewable (MW) fossil- fuel(MW) cost of fossil fuel(MW) 00.00 - 01.00 2000 1800 2000 30 01.00 - 02.00 2300 2500 2000 30 02.00 - 03.00 2500 2700 2100 45 03.00 - 04.00 2900 3100 2100 50 04.00 - 05.00 2700 2600 2500 45 05.00 - 06.00 2400 2000 2700 50 06.00 - 07.00 2200 1800 2000 36 07.00 - 08.00 2100 1600 2000 36 Assuming that the renewable generation incurs zero cost, determine an optimal generation schedule(specifying the amount of renewable generation and fossil fuel generation used in each period, the cost for each period and the overall cost for 8 hours.)
What is the high series capacitance winding on high voltage power transformer ?
Advantage of LT panel vs HT panel
what will happen if earth of 33 kv cable (earthed system) is not connected to earthing pit?
What are the basic properties of signal flow graph?
what is the difference between active power and reactive power and apparant power in practical as well as theoritical
how to select size of hardware for linking aluminium busbar is it depend on area of busbar or current flowing through bus bar
We have two APFC panels in same station. I need how to connect CT in two APFC panels.can we take one CT in series connection or two separate CTs.
Can 4pole (3 phase+neautral )RCCB proper functioning in only 3 phase load (no neautral, no Earth) ?
what is mean by parallel operation of permanent magnet generators