Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

I have connected 04nos. earthings to a transformer through
04nos. earthing pits seperately. 02nos. earthings are
connected to T/F body, and 02nos. earthings are connected to
T/F neutral.T/F capacity is 2000KVA, 11KV/415V. But after
completing of 02 years successful operation ,we are
facing following problems-

1. CT/PT occured blast one time
2. HT cable box occured blast two times
3. One body earthing strip and one neutral earthing strip of
transformer are overlapping at some places. Whenever these
two strips are pressed at overlapped points, they made spark.

What is the reason of spark?

Please explain the reason & rectification of above problems

Answer Posted / k.bhaskar

I think your neutral earth pits resistance is not
good,ensure each earth pit resistance with out grid.The
reason for sparking may be body earth is good and some
potential is there in the neutral path.

Second ensure transformer core channel to earth connection
(inside).Measure the winding resistance and unbalance load
distribution may also cause developing voltage in Neutral.

Is This Answer Correct ?    2 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

How can i get my certificate of competency as an electrical supervisor? I have complicated my B.Tech from Uttarakhand technical university this year (2012).

4525


If any HVDC line is going with positive & negative(the negative usually have return path of current with earthing electrode). Now the question is if this HVDC earthed electrode which is using as return path and earthed any nearby 400kv or 220kv AC substation equipments. which will be the impact of this on AC substation & its equipment, how severe may be this and what should be the minimum distance require between HVDC earthed electrode and AC substation equipments? It's really an high engineering level question...Dare to answer and increase your knowledge.

1890


sir please send me previous year questions of jspl of electrical section through which i could prepare myself fpr the test.

1920


A cable with concentric PE conductor must be used with frequency converter circuits what does its means.?

1582


What is the diffrence (Technical & Construction ) between CBCT & Normal CT?

2043


What is the maximum percentage voltage drop (vd%)for a motor control center

2019


please explain to me how to calculate current,voltage,resistance with formula??

1440


1. Design a counter which counts 0, 4, 8, 2, 6, and repeats using: 1.a using JK flip flops 1.b using T flip flops 1.c using D flip flops

1952


what is the role of energy meter in distribution system ?

1190


What is Load sharing of Transformer ?

2039


What is the kiosk parts, about them and their functions ? If anybody have some PDFs files or details about this plz send it on tawhidfaisal@Yahoo.com

1939


Is there any rule to select the voltage of motor based on KW rating? What is the rating above which lt motor becomes the HT motor?.

1726


Please, if 1kw is equal to 1.25kva; how then do I know how many kva in 7.5kw?

1669


What is control system?

1218


how to calculate the lightning arrester conductor @ no of earth pits required

2132