if AVR fails in alternator. what will be the effect.
Answer Posted / pratap k s
it depends on the alternator field excitation circuitry. In
a brushless alternator with compound excitation the
alternator produces a high voltage around 440V with the AVR
disconnected and the AVR regulates the output volatge to a
set value say 400V even if the laod varies from 0 to 100%
| Is This Answer Correct ? | 3 Yes | 0 No |
Post New Answer View All Answers
How to Calculate Transformer Earthing Electrode Rod Size both Body and neutral Earthing ? Any Standard Formula? Please Suggted
Pleae send me last 5 years of Question book about RRB chennai.
how to calculate slip ring induction motor stator and rotor currents??
do we use neutral grounding for resistive balanced load? if we use what happen?
if grounding is notdone at regular intervals for long distance transmission, will the load connected at distribution end receive voltage during negativehalf cycle of the sine wave?
from which subjects most of the technical que will b asked for hpcl(electrical).pls help me
What is the fault or needs to be done when frequency in ac drives is not changing?
if we give 60 hz single phase supply to the transformer used in europe , than what will happen
How the frame size of a flange mounted AC induction motor is calculated?
what is the reqirred voltage in HT motor to get full RPM on no load test?
Why in metering Ct for ammeters ct secondary side is grounded for each Ct but not in case of CBCT (Core balance current transformer)..kindly some1 highlights the reason..is it because net flux is zero?
what happens if earth of 33kv cable is not connected to earthing pits? please send this query's answer to ngrm.sudha249@gmail.com
what is excitation/
What is expention fastener (Fan)
1.why should we connect the measuring instruments in l.v side in short circuit test of a transformer? 2.why the power factor is less in open circuit test of a transformer?