What is vector group? What is meant by DYN11?Why is it needed?
Answer Posted / sukhdev negi
Abobe two reply explained correctly "what is vector group".
The answer to the last question "why it is needed" is as
follows:-
By virtue of constrction & terminal connections of the
transformer, a phase difference between primary vector &
secondery vector occurs. We need to know the same for the
following reasons:-
1)Matching of vector group is required (to avoid
circulating current/ fault ), when 2 transformer need to be
operate parallal on a common bus/system.
2) to provide transformer differential protection correctly.
| Is This Answer Correct ? | 16 Yes | 11 No |
Post New Answer View All Answers
'documenˁ
As we know diode work on both negative and positive but converting ac into DC we have to given a/c from negative of diode or positive side.please give me answer.
Explain Need of a starter in a dc motor.? Also explain any two starting and speed control method of dc motor?
1. Design a counter which counts 0, 4, 8, 2, 6, and repeats using: 1.a using JK flip flops 1.b using T flip flops 1.c using D flip flops
I am doing apprenticeship training at HT switch yard in NLC. How can i get electrical c license. ??? What r the rules for getting it as an apprentice? ??
how much maximum load a 2 core (Single phase) 16mm aluminium wire can take ?
what is the stear deltaprinceple?
How do you calculate the actual power consumption of an inductive load appliance. Say, a deep freezer of 200watts
What is meant by derating factor?
why magnet has north and south poles only why not east and west and why we are considering as north and south poles? why cant we consider as east and west?
Can any body tell gulf interview question for experienced electrical engineer ?
what is the profesional board for electrical engineer what is thepast and during construction for electrical engineering
Terminal blocks is used for segregate the connections... There is any principle for terminal block..?
how we will deside the high voltage value
if we install two earth pits with a clear space of 5m without any interconnection,by checking the digital multimeter will it show continuity between earth pits? If so what would be the approx. value