Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

What is the harm if we install primary side 11 KV VCB at a
distance of one Km from the 11/3.3KV 12.5 MVA transformer
through 11 KV cable.

Answer Posted / khor

No harm at all,but finding cable is a problem.11kv cable
supply for 12.5MVA must carry 650A per phase which is too
big for most standard cables.Standard VCB are 630A,1250A &
2000A,2500A.The more commonly available large size 3-core
300sqmm 11kv copper(450Amp) or alluminium conductor
cables,which is still flexible and can be transported &
coiled in drums of 250 to 300 metre lengths.There are
500sqmm 11kv 1-core xlpe/awa/pe cables available.
If you use only one transformer which is more
economical,the 3.3 KV side will be more than 2187Amp(plus
additional amp on losses and fans).While you can find 2500A
VCB,you will need more than 600sqmm copper conductors which
is not flexible/practical.
For the better/optimum design,seperate the final 415V and
3.3KV loads required and divide them into 2 groups and look
at the MVA and size them in seperate circuits.If 12.5 MVA
is all in 3.3Kv then employ 2 Main transformers where you
are not putting all the eggs in one basket.You need to
remember to look at the short circuit capacity( in KA 1 sec
or 3sec ) of the cables in circuit where small MVA is
involved.For e.g.1 MVA needs 52A @11KV but you cannot use
35sqmm cables,as it will blow like a fuse during fault
situation.
1 km of cables will have quite enough impedence to
limit/lower the fault level of the system.Protection of
this cable can be done with Pilot protection relays on
sending and rereving end,operated by class X CTs mounted in
the 11KV VCB panels.1 KM of Pilot wires of 2.5 sqmm 7-cores
alomg this cable is requird.So far I am assuming that it is
uderground cable is used.For Ariel Bundle Cable,3-core 185
sqmm aluminium is available.

Is This Answer Correct ?    3 Yes 2 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

why chock were used in old tubelights but are not newest tubelights?

2011


i have interview in Pepsi company what type of question will ask please send the question and answeer

3522


What is the HVDC Transmission System? What are the conditions applicable to lay an HVDC Line?

2352


If we have to feed a housing complex having load 8MVA, than what would be the better option, either we first step down 33kv supply into 11kv & than 430v or we proposed no of 33/.44 kv transformer, also which option is economical?

2275


What is the difference between vector surge relay (78) and Pole slip relay (98G)

1267


what is the difference between circular wdg & ractangular wdg?

2099


How eddy current generation support the idea of train braking?

2067


Why the dc voltage drop during starting of emergency lube oil pump? The Voltage drop from 135kv to 125 kv for one min. before re-establish to 135kv?

2371


A parallel flow heat exchanger will perform better than a counter flow heat exchanger. State if the statement is true or false.

1320


why the active power flow of some line is increased when the active power of out is cut ?

2119


What are the different methodes for calculating the short circuit Current?

2117


What is diversity factor in electric installations?

1227


The specific heats of the gas at constant pressure and constant volume are respectively 1.0 kJ/kg K and 0.72 kJ/kg K; the value of R for the gas is

1188


What is bridge rectifier and explain with details

1982


If we have to find the inductance of a dc shunt motor then by giving dc supply or ac supply and what is the reason for it. (this example is from "to determine the transfer function of a dc shunt motor ")

2030