How would we calculate the no of earthing pits required
for motor /panel
Answer Posted / syed rafiudeen
18. The GI conductor sizes shall be as listed below.
(1). HT switchgear, structures, cable trays & fence, rails,
gate and steel column
50 X 6 mm
(2). PCC & MCC EARTH PITS
50 X 6 mm
(3). DB
25 X 6 mm
(4). Motor rated above 55 KW & above
50 X 6 mm
(5). Motor rated above 22 KW & up to 55 KW
40 X 6 mm
(6). Motor rated above 5.5KW & up to 55KW
25 X 6 mm
(7). Motor rated up to 5.5 KW
8 SWG. GI wire
(8). Lighting panels & local panel
25 X 6 mm
(9). Control & relay panel
25 X 6 mm
(10). DG frame, excites
50 X 6 mm
(11). DG & TX’mer neutral
50 X 6 mm cu flat
(12). TX’mer body
50 X 6 mm
(13). Push button station
8 SWG. GI wire
(14). Receptacles & welding outlets
8 SWG. GI wire
(15). Lightning Arrestor
25 X 3 mm copper
(16). PLC & WF panels
25 X 3 mm copper
| Is This Answer Correct ? | 16 Yes | 5 No |
Post New Answer View All Answers
What are the different types of transformers?
Dear sirs, pls check this 4-20ma to RS485 module datasheet,pls guve me some suggestions. http://www.szsunyuan.com/sy/pro_more.asp?Productid=539 Thanks. E-mail:yunianjiang99@gmail.com
How to decide the size of the capacitor for a single phase induction motor say 2 HP ??
What is the two pole structure?
Explain difference between stand by earth fault and residual earth fault protection?
Advantages of using generator circuit breaker (GCB) scheme in a power station ?
when we have to purchase the transformer by own i.e how much load will preferred HT connection?
all details of DG UPS HVAC
define superposition theorem thevnin theorem ,norton theorom?
What are Contactors? How they works and what its highest rating?
Which power will flow first if we switch on a motor Active or Reactive? How?
mention hazard experienced during installation
how i can calculate the size for fire cable
how to calculate power consumption in slip ring motor at different step
why should the lowest unit of a testing transformer ( cascaded transformer ) have higher power rating??