Answer Posted / thwosif_emrson
How to find out Iron & Copper lossed in transformer:-
1>Iron Losses:-
Iron losses are due to hysteresis and eddy-current loss
produced by the alternating magnetic flux in the iron core.
The iron losses are almost independent of the load and thus
are considered to be constant at all loads.
In order to determine the iron loss, one winding of the
transformer (whichever is the most convenient) is open
circuited. A voltage is applied to the other winding and
the power (watts) in this circuit is measured. This power
represents the iron losses. Copper losses under these
circumstances are negligible.
2>Copper Losses:-
Copper losses are the heat losses in the windings due to
the electrical resistance of the windings. The copper
losses are proportional to the square of the current and
therefore to the kVA output. These losses can be calculated
from the design data but can also be measured by a test.
This test is known as the short circuit test for copper
losses.
The short circuit test is carried out by short circuiting
one winding, thus causing the transformer to behave like a
coil having a leakage impedance equal to that of both
windings. A low voltage is applied to the open winding
sufficient to circulate full load current through the open
winding due to transformer action in the short-circuited
winding. Under these conditions, the flux set up in the
core is so small that iron losses can usually be neglected
and the wattmeter would give the total copper loss.
Is This Answer Correct ? | 39 Yes | 6 No |
Post New Answer View All Answers
Why frame of the motor is specified?. If we mention KW and voltage level,automatically frame is decided or separately frame is compulsory to mention?.
Discuss about gear cutting machines.
I'm looking for a softcopy manual set for a Credence ASL- 3000. Anyone know where I can get it?
why HT armoured cable does not glanding
two way ckt diagram can be drawn by how many ways? give diagram
i have some screw comprressor with 630kw power,i have established them with simple star to delta circuit,by the way there is so much inertia when the screw comprressors start, can you offer me contactors power with 400vac or any cataluge to choose the contactors
State norton’s theorem?
What is the drawback of static coefficients?
Why is the air gap between the pole pieces and the armature kept very small?
circuit diagram of trip circuit supervision relay
IF alternator SCR value will be high means what happen in alternator efficency at operating power factor of 0.8
what happen when increase or decrease size of lamp,light.glass.
How many size of cable required for a 300m long and 30kw inductive lode
What are the differences between single phase and three phase?
what is the reason the main breaker is trip during the motor is running? (some time the breaker is not trip)