what happens if power factor is maintained at 0.9?give me
the answer in technicall way rather than telling the
penality n all
Answer Posted / guest
See the first thing is Power factor is angle between
voltage & current. see most of our load is inductive, & in
inductive load current always lags the supply voltage. In
unity P.f.condition current & voltage always in phase with
each other.
since P=VIcos(angle between V & I )
Now for a constant power as your pf changes i.e. decreases
to keep power demand constant current has to be increase as
your voltage is constant.in this way your current
increases , it causes increase in your copper losses
(I*I*R), voltage drop(I*R). And to keep voltage constant
more reactive power has to be provide.
generally any supply company penalties for more demand of
reactive power.
| Is This Answer Correct ? | 11 Yes | 4 No |
Post New Answer View All Answers
What is domestic transformer? Draw the connection of domestic transformer.
what are the safety measures of induction motor?
what is mean by NPS (Negative phase sequence)fault? what is the difference between EFR & OCR faults?
how we design a pannel to start 10HP motor with the help of star delta starter?
In the magnetic fluxes, what is the role of armature reaction?
why we permissive overreach in distance protection.where it is applicable to use in long r short lines
why and where we use early make & late break contacts in protection?
single phase power supply give to separate one steel coup with water, what reaction create
In synchronization circuit what is the function of Interposing voltage transformer(IVT)and Reverse voltage transformer(RVT)
How can we findout the maximum efficiancy of Transformer? At which load?
What happened when capacitor connect series in ac circuit?
Please clarify, 1. Is it required to lay two runs of GI wire along with Armoured LT cable if it is laid between one big mains (63Amps TPN SDF) to small main (32A TPN SDF) with proper glanding termination? 2. If the armoured cable with proper glanding is laid from DB to CNC machine, is it required to run two runs of body earthing to the Machine from DB? 3.If the armoured cable with proper glanding is laid from Substation to Hangar, distance is approx. 100 mtrs, is it required to do earthing at shop area though the primary termination at substation is earthed through gland.
List few applications of d.c series motor?
how to calculate the torque of a motor?
What is different bewteen low or high impedance busbar protection scheme