cascade controller is feed back or feed forward or both
Answer Posted / rajkumar
its a feed back loop.
Cascade Control uses the output of the primary controller
to manipulate the setpoint of the secondary controller as if
it were the final control element.
Reasons for cascade control:
* Allow faster secondary controller to handle
disturbances in the secondary loop.
* Allow secondary controller to handle non-linear valve
and other final control element problems.
* Allow operator to directly control secondary loop
during certain modes of operation (such as startup).
Requirements for cascade control:
* Secondary loop process dynamics must be at least four
times as fast as primary loop process dynamics.
* Secondary loop must have influence over the primary loop.
* Secondary loop must be measured and controllable.
Reasons not to use cascade:
* Cost of measurement of secondary variable (assuming it
is not measured for other reasons).
* Additional complexity.
Is This Answer Correct ? | 18 Yes | 2 No |
Post New Answer View All Answers
How it the difference between force balance system and dispalacement balance system?
Describe the typical instrumentation used in monitoring the performance of a shell and tube heat exchanger.
Programmable Logic control.
Please send me the sample question of Instrumentation of hpcl/iocl exam. my mail id hihi_kiholo@rediffmail.com
Sir , i have completed my M.Sc In Instrumentation and presently working in Maintenance department 3 yrs Exp , is there is any possible for work in offshore ..
HOW TO SOLVE PROBLEM WITH ENRAF LEVEL TRANSMITTER 854 ATG THAT PASSWARD DO NOT Exist INTO TRANSMITTER TO ADJUST LEVEL WITH PORTABLE PET 847, WRITTEN WRONG PASSWORD , I AM SURE THAT DEFAULT PASSWARD (W2=ENRAF2) IS THIS TRANSMITTER NEED TO REPLACE SOFTWARE AND HOW?
what is the advantage of submersible level transmitter compare to ultrasonic level transmitter?
Im having problems with interfase betwen SPI v7.0 and SPPID v5.05. Previous versions of Intools shoul be fixed with SPPIDproj.ocx file. It was necessary to replace this file with one that allows the connection between different versions of SPPID. It is necessary in the current version to do the same?Thanks
What is PDS and PDMS ?
Introduce yourself which is not present in your biodata?
How is flow measured in square root?
what is the process to make control schematic ?
Why boiler chimney area oxyden sensor fixing?
Explain signal isolator
what are the selections available in configuring a burnout protection of a controller? thanks