Answer Posted / thowsif_emerson_csm team
Assumed the transformer vector group As DYn11;
1.1U1V1W-which is primary -Delta Connection
2.2U2V2W- Which is secondary-Star connection
3.join 1U& 2U terminals
4.Supply 1U-1V-1W 440v Measured
a.1U-1V
b.1V-1w
c.1W-1U
d.1W-2W
e.1V-2W
f.1V-2V
g.1W-2V
h.1U-2N
i.1V-2N
TO CHECK
1.1V-2W=1V-2V
2.1W-2V>1W-2W
3.1U-1V=1V-2N+1U-2N
From above check(1,2,3) the vector group of transformer is
tested.....
| Is This Answer Correct ? | 12 Yes | 0 No |
Post New Answer View All Answers
why are u join ntpc
I use 20 nos led tube 4feet, in pathway 100mtr approximate, so what size cable i use for lighting
why the projects getting loss?
Comment on the working principle of operation of a single-phase transformer.
upto how many load can v connect to stabilizer which is used for tv
what is the easiest method of short circuit current calculation ? pls. derive with a mathematical example in real life application.
How PSV sizing being done
What is Faraday's law
what is submersible pump?what is different between motor and sub motor?
Why we make earth connection with Transformer Body and What will be the minimum size of copper wire as per code with respect to KVA rating of Transformer?
What are the parameters of water ( Water quality )to be monitored in Centralised HVAC ( water cooler chillers )
Rules and standards of electrical control wiring ?
what reactive how to maintain
What is the type of earth fault protection used in battery? explain.
While converting delta into star or star into delta ,the three values of resistances remains unchanged .Find out the value?Let In star R1=x;r2=x;R3=x On converting into delta,R12=x;R23=x;R31=x Find the value of x