Answer Posted / thowsif_emerson_csm team
Assumed the transformer vector group As DYn11;
1.1U1V1W-which is primary -Delta Connection
2.2U2V2W- Which is secondary-Star connection
3.join 1U& 2U terminals
4.Supply 1U-1V-1W 440v Measured
a.1U-1V
b.1V-1w
c.1W-1U
d.1W-2W
e.1V-2W
f.1V-2V
g.1W-2V
h.1U-2N
i.1V-2N
TO CHECK
1.1V-2W=1V-2V
2.1W-2V>1W-2W
3.1U-1V=1V-2N+1U-2N
From above check(1,2,3) the vector group of transformer is
tested.....
Is This Answer Correct ? | 12 Yes | 0 No |
Post New Answer View All Answers
1600kva capacity Transformers how the bucholz relay,Oil temperature,winding,surge relay relays setting are to be done
How can we connect additional batteries to three phase ups? What are parameters we have to check when connecting?
I am getting above 60 V as open delta voltage against single phase unit ICT at tertiary delta formed and ICT getting trippped on NDR. ICT tested and found in order. PTs provided on tertiary are tested and in order. what may be the reason?
how to know the diffrential relay setting of 06mva step- down (delta-star)transformer?
define displacement & magnitude ?
what is the minimum pay scale for electrical engineer (building construction)in kuwait? plz revert back with yrs of experience & pay scale respectively.
why it is so called as xlpe(cross linked poly ethyline) cable?
What is a signal flow graph?
IF alternator SCR value will be high means what happen in alternator efficency at operating power factor of 0.8
types of central Air conditioner plant?
how to calculate maximum current
Difference between Earthing Truck & Earthing trolly for HT panel
WHAT IS DOL STARTER? HOW IT WORK? GIVE ITS CONTROL AND POWER DIAGRAM .
which VFD is better ( LT or HT)
How to calculate Voltage regulation of 22 KV Over head Line.