Can someone give a detailed chart on the temperature ranges
which can be measured by various temperature sensors.
Answer Posted / rajkumar
Thermocouple
Type Useful/General
Application Range Notes
B 1370-1700°C
(2500-3100°F) Easily contaminated, require protection.
C* 1650-2315°C
(3000-4200°F) No oxidation resistance. Vacuum, hydrogen or
inert atmospheres.
E** 95-900°C
(200-1650°F) Highest output of base metal thermocouples.
Not subject to corrosion at cryogenic temperatures.
J 95-760°C
(200-1400°F) Reducing atmosphere recommended. Iron leg
subject to oxidation at elevated temperatures--use larger
gauge to compensate.
K** 95-1260°C
(200-2300°F) Well suited for oxidizing atmospheres.
N 650-1260°C
(1200-2300°F) For general use, better resistance to
oxidation and sulfur than Type K.
R 870-1450°C
(1600-2640°F) Oxidizing atmosphere recommended. Easily
contaminated, require protection.
S 980-1450°C
(1800-2640°F) Laboratory standard, highly reproducible.
Easily contaminated, require protection.
T** -200-350°C
(-330-660°F) Most stable at cryogenic temperatures ranges.
Excellent in oxidizing and reducing atmospheres within
temperature range.
RTD Resistance Wire Comparisons
Element Metal Temperature Range Benefits Base
Resistance TCR (Ω/Ω/°C)
Platinum -260 to 850°C
(-436 to 1562°F) Best stability, good linearity 100 Ω at
0°C 0.00385 (DIN-IEC-761), 0.003916 (JIS 1604-1981)
Copper -100 to 260°C
(-148 to 500°F) Best linearity 10 Ω at 25°C 0.00427
Nickel -100 to 260°C
(-148 to 500°F) Low cost, High Sensitivity 120 Ω at 0° C
0.00672
| Is This Answer Correct ? | 4 Yes | 1 No |
Post New Answer View All Answers
i have steam drum height 1000mm. and i want to placed the transmitter below the tap.how i calculate.
What are advantages and disadvantage of the ac supply load cell?
What are different types of control valves?
What is difference between differential pressure & delta pressure?
how will you segregate the alarm levels in alarm management system during factory Acceptance Test
What is the procedure of calibration of Load cell?
Why upper weighing limit of electronics balance is 90% of the total weighing capacity?
In turbine what does term CDP, NI, NH, HSSOC means.
POSSITIVE PULSE IS APPLIED TO AN INVERTER INPUT.THE TIME FROM THE LEADING EDGE OF THE INPUT TO THE LEADING EDGE OF THE OUTPUT IS 10 ns. THE TIME FROM THE TRAILING EDGE OF THE INPUT TO THE TRYLING EDGE OF THE OUTPUT IS 8 ns. WHAT ARE THE VALUES OF tPLH and tPHL?
Why all the drains(Gland sealing,ESV,Casing inlet etc) are directly connected to the flash tank instead of hotwell of the condensor in the power plant? My Email Id:naba02222@gmail.com
why use 50% lel methane gas concentration for gas detector calibration instead of 60% lel gas concentration whereas the hi alarm set at 60% lel.
what is the reason while warning lamp is on while the engine is cranking?
Im having problems with interfase betwen SPI v7.0 and SPPID v5.05. Previous versions of Intools shoul be fixed with SPPIDproj.ocx file. It was necessary to replace this file with one that allows the connection between different versions of SPPID. It is necessary in the current version to do the same?Thanks
Explain how thw analog to digital converter works with the circuit diagram
If we increase only P what will be controller action ?