What is minimum distance between three thermocouples (2oo3)
mounted on same pipe line (20")?
Technically accepted by stright line mounted or circler
mounted?
Answer Posted / rajkumar
120 degrees in the same plane (circular), especially if
there has not been sufficient thermal mixing of the process
at the point of measurement. In this case, the average of
the temps should be used for control (as opposed to the
middle of 3) in addition to any deviation checking used to
detect a failed TC.
If any thermal streaming is occurring, then mounting the TCs
linearily down the pipeline reduces your chances of
measuring it.
| Is This Answer Correct ? | 3 Yes | 3 No |
Post New Answer View All Answers
what is the criteria to decide conductor size of a cable ?
what is the vital subject for scoring bhel exam&what is the question pattern
i have steam drum height 1000mm. and i want to placed the transmitter below the tap.how i calculate.
why we use the ac supply load cell>?can we use the dc supply load cell?advantages and disadvantage of the ac supply load cell?
types of cable..? Use of every types of cable..?
Which topics are covered in Process Control?
How to Calibrate Level Switch in field
What are the error values can accepted in flow transmitter calibration?could u give any formula for this?
What is megering????
What is the advantage of using locally fabricated hook ups over Pre fabricated hook ups in process instrumentation?
1- Explain about HPM 2- What is the FSC and explain the configuration of FSC 3- explain the complete loop of vibration, how it works (field to control room) 4- What is the use of proxymitter? 5- During job your partner effected with H2S then what you have to do. 6- what type of gland packing uses when valve glind is leaking.
wich is coming the first HAZOP OR SIL
What is the reason PT speed not incresed in gas turbine?
can anyone tell me about the basic concepts to consider before to start a PLC panel wiring
Differentiate between ultrasonic flowmeter and radar type flow meter