What is the major difference between P.T. & C.V.T ? Why CVT
is used in HT Transmission line in place of P.T.?

Answer Posted / engr. l. o. osuji

Hi Sharma,
Answer #2 is correct but let me add more to it. For
voltages like 11 and 33kV the voltage transformers may be
referred to as P.Ts unlike 132kV etc where CVTs are used.
For either 11 or 33kV the magnetic part with iron core is
not bulky hence are used directly to step down 11 or 33kV
to say 110V used for protection and metering.
In the case of CVTs series capacitors are used to drop down
(note, not stepping down) the voltage i.e.like a voltage
divider from 132kV to a manageable value that can be
transformed like the 11 or 33kV P.T. Take a careful look at
the CVT you will find out that the bottom part is the
transformer part. That part may be transforming say 13kV to
110V. If 132kV were to be transformed directly to 110V then
the voltage transformer or P.T as it were will be so bulky
that there may be little space for other devices. Both are
for the same purpose but the use of each depends on the
voltage level.

Is This Answer Correct ?    174 Yes 18 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

What is instrumental error?

680


What is Delta Connection? What is meant by Forward Delta & Reverse Delta & How Will be the Connection in Power Transformers?

1799


what is acceptable leakage current for 33kv cable while doing high voltage test for cable? how to calaulate the leakage current for 33kv or any rated cable?

3431


What is difference and reason b/w -48V BTS system and 24 V BTS system. Plzzzzzzzzz tel me.

1717


Is there possible to Test Transformer for Overfluxing Capability. Or is there any firm who does Overfluxing Test on Transformer?

2629






What is the difference between a Root Locus plot and a Bode plot?

763


why there using acb enclosure in big buildings

1521


What is mean by spike arrester(Voltage Operated)

1598


we have two generators different capacity on 15 MW and other 6MW at 11 KV , 15 MW gen. bus short level current 40KA,and 6MW short level current 25KA,, length of cable 100MTR between 6 MW from 15MW gen. for bus coupling . kindly tell any one can we use both NGR OR one NGR from any GEN. BOTH NGR has diff. rating. Tariq pakistan

1213


An 8 pole, 50 Hz, 3-phase IM is loaded to a poing where pull out torque will occur. The rotor resistance per phase is 0.3 ohm and motor stalls at 650 rpm. The slip when motor stalls is A 1 B 0 C 13.33% D 10.33%

1406


Explain how you intend to work under pressure to meet up with deadline target?

4704


how is control wiring coding is done in a CRP panel ?

1531


How to calculate VCB rating for 33KV ,25 MW Power line?

1225


what is control supply rating of a machine

1482


compare between starting charactristics of synchronous motor with those of 3Q Squirrel cage induction motor

1267