Can I use measuring current transformers in protection
purposes?
Answer Posted / minu
no u cannot. this is because the metering and protection CT
cores are differently designed and r made up of different
materials. A Protection CT core is designed so as not to
get saturated at very high fault currents which can cause
mal-operation of the relay connected to that CT. Also, the
accuracy required in the metering CTs is higher than that
required in the protection CTs.
| Is This Answer Correct ? | 28 Yes | 0 No |
Post New Answer View All Answers
If you have an earth with pilecap then your resistance is really low. why and how?
Is it possible to obtain 480v or 550v in single phase output by giving the input to 230v to a single phase torodial type transformer without using a stepup transformer?
100 MVA 3-phase alternator with earthed neutral has a reactance of 5 ohms per phase. what will be the fault MVA of generator.
How many double suspension hardware fittings are required on a double circuit transmission tower?
whatare the disadvantages occur,if the form factor of transmission will not be equal to 1.11
0.5,1,1.5,2.5,4.0.6.0,10,16 square mm electrical wires how much take maximum current in 50htz
What is ideal IR values for ground and neutral.
what is reverse power relay brief explanation and in b/w where it is connected
Why human body feel electric shock?
State the types of distortions in amplifier?
WHAT R THE SAFETIES IN A HIGH TENSION PANEL N LOW TENSION PANEL. ALSO WAT SAFETIES R THERE IN A 200 KVA TRANSFORMER?
How to select cable the size, what is the parameters use and what is the formulas use for this cable size calculation?
what is the calculation formula for motor starting torque,running torque, running torque.
132/6.6ππ πππππππππππ πππππππ πππ πππ πππππ πππ πππππππππ. πΈ'ππ πππππππ πππππππππππ ππ 6.6ππ/415π πππ πΈ πππππππ πππππππ ππ ππππ πππππ πππ ππ ππ 13/6.ππ πππππππππππ?? πΈπ π½π.. ππππ π ππ’??
WHY NUTRAL GROUND SYSTEM USED IN 33KV SYSTEM