Answer Posted / karanth.sp
The PF of the connected load to a particular transformer is
to be asssuemed or known exactly.If the transformer is
already loaded you can kow the running PF by PF meter
connected.IF the PF is say 0.7 & you want to improve to
unity.You must add a capacitor of Total load in KW multiply
by a factor of 1.02.That is the value of Capacitor in KVAR.
Formula is PF (cos0)=0.7 Tan01=0.963
improve PF(Cos0)=1 Tan02=0
KVAR Required= P(Tan01-Tan02)=P(0.963).
This shall be devided in to number of stages as required.
| Is This Answer Correct ? | 9 Yes | 5 No |