why dont we connect the two 12 V DC batteries in parallel,
for an inverter (UPS)?
is there any harm ?
Answer Posted / jun dela cruz
you can not connect two or more batteries in parallel even
if they are identically the same. No two batteries have same
terminal voltage and internal resistance which will produce
circulating current between them. This condition will
discharge the batteries even without load. Although you can
connect batteries in parallel while charging only.
| Is This Answer Correct ? | 12 Yes | 4 No |
Post New Answer View All Answers
How to test the vector group of a Yd11 transformer? what are the relations to be checked between various vectors to confirm this vector group?
What is a Phase shift meter? Where can I get one?
a simple c++ program to calculate simple interst with its data members as private
What are the main significances of root locus?
at what base you will tell the direction of rotation of dc motors and generators?
Can double compression glands be used with regular cables?
what is maxemo work permit procedure
a 230v transformer with step down ratio 19:1.it has 2000turns on primary and rated 25va calculate max primary current no of secondary turns volts/turn
what is sevice settings for mccb?How can be it setted?
Classify drilling machines.
What is value of earth resistance required for substation and equipment earthing and what are the reference guidelines
what is the maximim current drawn by 1 phase and three phase welding machine
What happened when voltage will half value of current ...
i need to now what will be the cable size to the following load, transformer to distribution panel distance 110m, load 1000kw, voltage 400v, pf 0.85, permissible voltage drop 2.0%, overhead line, atmospheric temperature 35 degree c.
How delta connection in the primary of distribution transformer reduces harmonics?how delta connections reduces harmonics?Please answer me...Hope that question is correct.