What is the harm if we install primary side 11 KV VCB at a
distance of one Km from the 11/3.3KV 12.5 MVA transformer
through 11 KV cable.
Answer Posted / raj
Nothing harm in placing the breaker beffore 1km distance,
but the system will suffer with the following disadvantages.
1) One KM long cable protection has to be taken care which
will cost heavily.
2) local supply providing authorities may object, since
this kind of arrangement is not allowed as per ie rules.
3)Running the pilot wires for the protection signal
sampling and the control wiring of the breaker will become
a tedious job.
4)Proper and cautious co-ordination is required in the
operation and maintenance point of view before every
operation.
| Is This Answer Correct ? | 14 Yes | 2 No |
Post New Answer View All Answers
What happen to generator if i have unbalanced load?
why d.c produces corrosion
what is transient voltage?
If Dg set load increase 25%, How much increase fuel Consumption (15 kva 2 cylinder DG set)
i had aplied Hindustan Petroleum corporation limited for the post of maintenance technician -Electrical,i want model questions,if anybody have please send it or please advice?
A 500 V shunt motor runs at its normal speed of 250rpm when the armature current is 200A. The resistance of the armature is 0.12 Ω. Calculate the speed when a resistance is inserted in the field reducing the shunt field to 80% of normal value and the armature current is 100A.
In three pin plug 6 amp. 220V ac rating. Why earth pin diameter is higher than other two pin? What its purpose ?
control & auxilary circuits used for circuir breakers
how does a submersible pump work..?
What is the test block protection relay if any body know plz explained
What is the limitation of kirchoffs law?
Explain the working of any one cutting machine
why Lightning arrestor are made by 2 seperate stack of inslutor but why cvt are in single stack of insulator.
What are the symptoms of a bad PG card of a drive (inverter) esp. of Yaskawa Ac Drives (inverters) G7 ?
What it the purpose of parallel phasing transfomers??