why motor starting current is High ?
Answer Posted / electrical
V=Eb+IaRa,Eb=back emf
At starting there is no back Emf
And V (Normal Supply Voltage)=220V(single Phase)
Ia = Armature Current
Ra = Armature resistance(Usually less (.2 to .5 ohms)
From the Above equation,
Ia = (V-Eb)/Ra
Since Eb is Zero, the above eqn will become
Ia = V/Ra (220/0.5 = 440A)
So at starting the current thru the armature is very high
to minimise this we are using the starters.
| Is This Answer Correct ? | 24 Yes | 1 No |
Post New Answer View All Answers
why we are not giving the zone 1 trip command to the master trip relay
Sir 33kva 2 transformer load 900 amp calc 1800 amp mana jayega
why swinburnes test cannot be performed on series machines?explain
for compensate 315mh inductance ,how many capaciance required?
Generator,motor and alternator Working principal Please explain easily
in an electronic tri vector meter when the current and voltage sequence changes ? what is the effect of phase sequence on recording of meter
How many capacitors using in LT panel as per Govt rules?
what are the problems that generally occur in power flows??
Why can't we take NO LOAD TRIAL of motors having V1 mounting??
what is the purpose of slope in the differential relay?why we are using two slope?but in busbar differential we are using only one slope.why?
What do you mean by power transformer?
in 6.6 kv vaccum circuit breaker vaccum bottole vaccum capacity ????
how do i work out the Amps of a incommer if i am running 1 37 KW motor and a 0,75 KW motor and some solinoids
block diagram of 2 ups system connected in hot stand by mode?
what is the relation between reactive power and power factor for the what is the limit of reactive power and power factor