Answer Posted / ayush chamoli
according to fortescue- unbalanced 3 phase voltage nd
current(during fault) r made up of three symmetrical
component having positive,negative nd zero sequence.
zero sequence-when all the symmetrical components r in
phase nd hve same magnitude.
+ve sequence- when symmetrical components r in 120 degree
phase wrt to each other nd hve same phase sequence as
supply voltage.
-ve sequence-when components hve 120 degree phase wrt each
other nd hve opposite phase sequence compared to supply
voltage(3-phase).
for 3phase(symetrical or balanced fault)- only +ve sequence
exist while zero nd -ve sequence r zero.
LG fault all sequences r equal.
LL fault-only + nd -ve sequence(as no ground thats why no
zero sequence).
LLG fault-all sequences nd hve different values.
| Is This Answer Correct ? | 67 Yes | 5 No |
Post New Answer View All Answers
How many Zones can be in Conventional type fire alarm system & how can we detect the fire in Conv. type FAS?
how can service sitting be setted for MCCB?Example for sittings IR (CURRENT RATING),IS(CURRENT STARTING)IO (current operating)?
What is nichols chart?
Why are lt windings placed near the core?
What is Auto Mains Failure Panel & Auto Synchronizing Panel
how to remover corona effect and hysteresis losses from contactor
why capacitive load is not used in routine life????any reason is there ??????
How equivalent impedance is calculated in thevenin theorem?
brief notes on ammeters
According to IEC60034-14, When the vibration monitoring system required for motor Bearing. above which KW, it is required? and for what type of bearing the vibration probe is provided.
plz send me the syllabus or any sample paper for engineer trainee recruitment if any,on ravinder911@yahoo.com
how freewheeling diode improves the powerfactor
defult setting in p220 micom motor proction relay for 11kv,640kw,f.l.a.-40a,1440rpm ht motor?
how to find three phase complex power in per unit and MVA?
I am getting above 60 V as open delta voltage against single phase unit ICT at tertiary delta formed and ICT getting trippped on NDR. ICT tested and found in order. PTs provided on tertiary are tested and in order. what may be the reason?