Answer Posted / pundlik wanwe
Generator is normally feeds power to the infinte grid which
is having a number of generators connected.
If by some reson turbine gets tripped but if GCB not get
opened in that case there will be a reverse flow of power
from grid to stator wdg and the generator will behave as a
induction motor. In this case there will be a heating of
rotor end ring and and outer wedges of the same which will
in turn damage the rotor winding. To avoid this reverse
power flow is resricted by tripping the generator on
reverse power flow.
| Is This Answer Correct ? | 48 Yes | 3 No |
Post New Answer View All Answers
What are the advantages of stationary armature and rotating field system?
why u r living from presentaly working.
how to calculate differential current when we testing differential relay..suppose we have 1000kw generator,630amp VCB,what value we should put /inject so that relay trip the VCB? PLLZ justify ur comment
how to identify the cable quality and what is flame proof cable
what is efficient motors and how it is different from normal induction motors
What is mean by hot and cold loop testing?
What is the important precuations need tocarried out while working with Electrolite in Battery PM?
An impedance of 100 ohms resistance and an unknown inductance is connected across the capacitor. The resulting impedance is a pure resistance of 500 ohms ifω = 10^5 rad/sec. calculate the values of inductor and capacitor.
I want formula to calculate current loss with distance in km.I searched many sites but didn't right answer.Plz reply me
how cables go in and come out for distribution from the feeder pillar box?
what does a k rating in a transformer means?
TO CALCULATE THE RESISTANCE OF GRR OF HT MOTOR 400KW WHEREAS STATOR VOLTAGE 6.6KV AND ROTOR VOLTAGE 705V AND ROTOR CURRENT IS 346A.
It is desired to flood light the front of a building 42 meters wide and 16 meters hig.Projectors of 30 degree beam spread and 1000 watt lamps giving 20 lumen/watt are availabl.If the desired level of illumination is 75 lumen/m and show a suitable scheme.Assume the cofficient of utilization, deprecitation factor and waste light factor are 0.4, 13 and 1.2 respectively.
How we can calculate the consumption in kwh of motor on basis of kw @100% load, @50% load & @ no load.
hi Is there any possibilities to find out the rotation of a shaft or something else by using electromagnectic waves or by IR rays.If s then can v change the dir., of rotation of the same by remotely?& how? plz dn't any1 say "NO r CAN'T"