Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

How can we calculate the fault level of the distribution
system knowing the percentage impedance of transformer &
subsequent equipments.

Answer Posted / pankaj

THERE IS A SIMPLE CALCULATION IF ASSUMING INFINITE SOURCE
BUS THE MAX LEVEL OF FAULT AT LT SIDE OF A 11/0.433 5%
1000KVA TRANSFORMER CAN BE CALCULATED AS:

KVA*100/SQRT3*433*Z% kAMPS

1000*100/1.732*433*5 = 26.7kAMS

Is This Answer Correct ?    39 Yes 7 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

if sf6 gas low in gis what will happen

807


best manufacturer for busbar for outdoor switchyard having double bus bar scheme, can any one share technical specification of busbar. 132kv voltage ?

1697


What is mason's gain formula?

1283


How to select the earthing transformer,for DELTA TO DELTA TRANSFORMER OR ALTERNATOR SIDE.Pls post your answers and calculation.

2352


how to select fuse rating for a 3-phase motor ???

1783


how technical is calculated in 11kv line and lt line

2027


how we can calculate the efficiency of a diesel generator ?

1682


what is mean by kneepoint voltage? when it will happen? ( my doubt is, if CT secondary is open means ct get saturation or blas? what are factors are required for calculations? plz give currect anws:

2014


what is the safe meggar values for motor, transformer HT, LT and Cables? IF we want to replace I/C bay at our 220 kv substation which is of 140 mw load capacity bay to be replaced by 400 mw capacity bay.other than CT(1200/1) what are the other equipment i have to replace. why we generally use 3.5 core cable or in other word 1/2 core for neutral and also confirm me that in balance conditiob(3 phase)current in neutral will zero

2253


What are your personal skills and abilities for such a Master Course and your possible preparation to undertake this course?

2024


why is control bus bi-directional?

2133


how much maximum load a 2 core (Single phase) 16mm aluminium wire can take ?

2620


(In MEP services) HVAC in AC Plant room what else can we provide if the chiller is not considered?

2030


Why do we use copper cable for HT Supply and why not Aluminium?

1996


When color of silica gel will gets change from blue to pink from Top to bottom?

1583