How to test Power Transfomer vector group in the field?
Answer Posted / chicoybolanio
Put the tap position on the nominal taps.
Connect the 4 core cable with MCB on the HV side and the
leads cable at LV side and make sure that
the LV side in open circuit. Then loop together between HV
red phase and LV red phase.
Inject 415V (Switch on the MCB) at HV side and measure the
voltage at LV side for each phase. record results and by
using the test result and following proper scale draw the
vector group of the transformer winding.
| Is This Answer Correct ? | 11 Yes | 1 No |
Post New Answer View All Answers
What are the advantages of instrument transformer?
is it true there's a big difference in using Cummins or Denyo...especially power output or leakage
hii this is ranjith from hyd... i want to know what type of questions they ask in interview...and hw the interview will go..? what subjects thay ask specially for electrical engg students?
Brief me about maintenance planning & sheduling of machine tool.
what is the criteria for selecting fuse rating in 1phase, 2phase & 3phase welding sets?
WHICH SIZE A.B.CABLE IS USED FOR 11KV.
Why we find the sensitivity for the CT's to check?
To prove the capacity of a 10MVA transforemr with 6.5% impedance by a short circuit test how much power is needed to inject an impedance voltage if we have to arrive for its rated current?
what are the main applications of transistor in non-linear region?
what about the power of wattmeter at starting and loding?
WHERE NEUTRAL WIRE IS CONNECTED AT DOMESTIC TO TRANSMISSION LINE(SINGLE PHASE TO THREE PHASE)
what is vA rating and class of a ct.
What is Negative Potential Bias
AL=0B9H,bl=75H, ADD AL,BL AL=____________? CF________? OF___________?
For a three phase induction motor, what will be the effect on motor if the neutral of the system is shifted to say 20 deg.?