Can we use the 60 HZ transformer/rectifier/Motors/Coils in
50 HZ? if not so, why?
Answer Posted / pratheesh
NO...
For maintaning the magnetic flux in any coil(motor.
transformer etc.)in the same level, we have to keep the v/f
ratio same always. Where V= Applied voltage and F= Applied
Frequency.
If u reduce the frequency from 60hz to 50(reducing to 83%)
hz by keeping the applied voltage same, that instrument
will take more current.
one reason for that is while reducing the frequency, its
inductive reactance also will decreace, so total impedence
also.
But you can use that machine if u reduce the applied
voltage also to approximately 83%
| Is This Answer Correct ? | 15 Yes | 0 No |
Post New Answer View All Answers
PAC and simple Ac different
What are the causes for the failures of sandwich type (Al) busducts?
How to calculate the time setting for star connection in star delta starter? For example 10KW 3PH Induction motor.
Why do we avoid electrical conduits in floors at apartments?
whatis the commertial spec. of distribution boards ?
what is the series parallel connection of capacitors? and how can we use these application in three phase motors for controlling torque?
what is droop control?
STATE WORKING OF VACCUM CIRCUIT BRAKER?
Can the output voltage of a rectifier be greater than the input AC voltage without the use of any voltage multiplier in the circuit??please provide the explanation too..
what is the difference between the characteristics of two different phase bushing of any transformer
What is the meaning of floating point earthing in battery backed systems ?
HELLO EVERYONE, I RECENTLY HAVE FOUND ONE PROBLEM, I WAS TAKING NO LOAD TRIAL OF AN HT MOTOR 920 MOTOR , 1440 RPM , 6.6 KV, WITH AUTO TRANSFORMER. AT 450 V, LOAD WAS 40 AMP AND SPEED WAS 250 RPM. BUT AS WE INCREASE VOLTAGE FROM 450 TO 480V, LOAD BECOME 41 AND SPEED REDUCED TO SOME RPM . SO WHICH PHENOMENON ACTED HERE FOR REDUCING SPEED.?? AND IS IT HAPPENING ALWAYS OR IT IS RARE? I ALSO HAVE FACED SUCH PROBLEM WITH FEW LT MOTOR ALSO.
Greeting to all members, How to calculate spill current when we have different ratio CT and Class for REF(Low Imp) I have 500/1A 5P20 @line side n 400/1A CL.X @ Neutral.
how to work droop ct in generating station
What do you understand by oldham's coupling ?