Answer Posted / guest
hi sanjay
1. AIR SUPPLY
I/P input - 1.4kg/cm2
Out put - 0.2 to 1kg/cm2 ok
2.input signal= 4-20 mA
i.connect the air supply to input with the hepl of REGULATOR i.e 1.4kg/cm2
ii.connect the MASTER GAUGE to OUT PUT ok
Apply the signal
i. 4mA- 0 kg/cm2 (if not Zero/0.2kg/cm2 Adjust Zero adjustment Screw)
ii. 20mA-1 kg/Cm2 (if not 1kg/cm2 Adjust Span adjustment Screw) ok.
then 8, 12, 16mA.
min. and max. is ok the remaining will perfect automatically i.e 8,12,16mA.
and MAIN IMP POINT is ON the I/P's Ckt board Side 4 adjust ment buttons is there and adjust that buttons Direct and Revese Actions ok
| Is This Answer Correct ? | 20 Yes | 0 No |
Post New Answer View All Answers
why we are using magnet for calibration of gas detector?
How does your previous experience relate to the job you are applying for ?
Give 2 application of quartz crystal used for process parameter measurement.
what is sil (safety integrity level
pls provide me syllabus and old question paper of instrumentation engineering for GET(JSPL)
How to convert milliampares into flow??
can any send me a forbes marshall dtron 316 manual
What are the charcterstics of a P&ID controller block for Governor speed raise or lower for a load sharing functionality between 4 Gas turbines in droop mode.
what are the definitions of input, output, command & signal according to instruments controlled by PLC using DCS System?
1. For Steam drum level signal, why do we compensate with drum pressure signal? 2.For main steam Flow signal is comensated with main steam temperature signal and main steam pressure signal why?
In power plant to measure vibration of a turbine we install sensors. Before install this sensor we have to set gap voltage. What is meant by gap voltage and its use?
How do you identify an orifice in the pipeline?
all types of liquid analyzer principle with drawing?
can we create an interrupt in plc through scada?
how radio frequency level probes works with its controller ? what is its principle ? pls give me brief explanation?