how you can select circuit breaker for 2000kva transformer?

Answer Posted / sareer ahmad lone

Ans.First you have to find out the full load current of the
transformer that is IL=2915A then as per NEC you have to
give atleast 25% that is 2915x1.25=3643.75A.So the nearest
size of Circuit Breaker shall be 4000A.

Is This Answer Correct ?    8 Yes 6 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

What is The Resistance Formula

775


what is thermal resistance of PVC Cable.

1347


Can we use BS 6651 and BS EN 62305 standards for computer room lightning ptotection in substation?

1735


Single line diagrams for star to delta and DOL starters.

1810


CT Ratio of a energy meter connection is Red Phase : 100/5A, yello Phase : 50/5A & Blue phase : 100/5 A what is the overall Multiplication factor

1196






What is dynamo?How it works and what is the function of dynamo in a DG.

1582


what is KSR type transmission tower? What is LSR type transmission tower?

4627


What is the different types of cable & current capacity of cable

1444


What is Long rod insulator and it's applications..? merits over the disc insulator ..?

1436


What happen to generator if i have unbalanced load?

1648


Is there any rule to select the voltage of motor based on KW rating? What is the rating above which lt motor becomes the HT motor?.

1224


What is the equivalent circuit of a transformer and its vector diagram?

2163


Why star delta starter is preferred with induction motor?

626


why the making current is more than then the breaking current and if its true then its about a controling circuit or breaker power contact points

1607


how to calculate the lightning arrester conductor @ no of earth pits required

1601