can we use a control valve without positioner

Answer Posted / santosh nanavati

Yes, it can be used without positioner with the following
condition.

(1) Spring operating range should be 0.2 to 1.0 Kg/Cm2.
(2) If the application of the control valve for the
relevant process parameter control is not critical, the
valve can work without positioner i.e. it will give less
accurate output & control of parameter.

Is This Answer Correct ?    15 Yes 4 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

why use 50% lel methane gas concentration for gas detector calibration instead of 60% lel gas concentration whereas the hi alarm set at 60% lel.

2203


In most instances, Inertia processes are quite uncommon. Give an example of a combined Resistance and Capacitance situation.Describe an application, which according to your understanding of the subject matter, comprises of both Resistance and Capacitance effects.

1524


What is limitation of the ht.of the displacer of a level trol?

1837


How to calibrate the flow transmitter

1050


how will you segregate the alarm levels in alarm management system during factory Acceptance Test

1928






Why plc require in analog input 4-20amp & 0-10 volt?

625


Draw a simple circuit for a well head control panel used to protect the well against fire, leak, blockage, ESD, & controls the operation of one downhole & one surface safety valve. Explain the operation and controls

1162


How to find out the current of two motors having same power consumption but different RPM?

1541


What is the advantage of using locally fabricated hook ups over Pre fabricated hook ups in process instrumentation?

1592


Do you have reference list?

1428


What is PDS and PDMS ?

1695


need to calculate flow rate with the help of dp range and orifice bore dia and size. range is 0 to 400 inwc and orifice size is 12 inch 150 # rf and bore dia is 7.180 inch. need to calculation for flow rate

893


centrifugal compressor interlock? Tell me the parameter at which compressor will trip

2688


i have used level transmitter in starch cooking preparation tank. tank total height 2mtr.sometime LT display shows some error value when tank is fully empty and diaphragm side i already checked okay no problem in diaphragm area. field cable checked 24volt and mA shows correct value while tank empty mA is 4mA. 4mA i needed that 0% but display showing 10% or 15% percentage values are varying continously please give any good solution for me.....

997


what is droop in governer ,type of droop ,how it work

1767