how you can select circuit breaker for 2000kva transformer?
Answer Posted / ashish patil
First find the full load current of transformer.2MVA
transformer current value comes near 2915 A. consider
overloading capacity 10%. it comes near 3100.
so u can select indor Air circit braker or 4000A
capacity.
| Is This Answer Correct ? | 29 Yes | 13 No |
Post New Answer View All Answers
design a 3 bit synchronous and asynchronous counter using T- flipflop
I am designing new project sub station with 220 kV / 11 kV, 40 MVA capacity. This project have many recifier sets, which can generate 3rd harmonics. Now I have to select vector group of This transformer. To minimise 3rd harmonics, what care should I take in selection of Transformer Vecrtor group? If it is Y-Y with open Delta tertiary then what should be the rating & voltage of Tertiary Winding?
(In MEP services) HVAC in AC Plant room what else can we provide if the chiller is not considered?
can anybody tell me that for p.f. Improvment we use capacitor banks but how to decide its capacitance. As we all know how to calculate kvar but what abt capacitance value
How to check the cable fault / hv test of transformer cable.
why industry prefer ht motor instead of lt motor.
number of I/O devices in siemense plc
A 3 phase transformer's (Y-Y) Y and B phase is (Y and B connection not broken) broken from neutral and R and Nutral connection is ok, what will be the relay tripping and why
What is different type of Electrical curve and how it protects the equipment's while up-normal situation?
any one can explain the stages of a knee point which is taken during ct magnetising curve.
what is the voltage between earth to neutral in lift.
specific difference of ICT&Auto Transformer
what is an unbalance in acircuit? in a three phase 3wire circuit how an unbalance will come? in a three phase four wire system how an un balance is coming?
what is inter connected dc generator?
why high speed tripping relay will be used in tripping circuit why not normal relay