how to test generator protection rotor earth fault relay
and locked rotor test?
Answer Posted / gajanan koshatwar
generator earth fault relay basically monitors the
insulation level of roror winding and shaft ground. The
rotor earth fault relay injects the low frequency pulse in
one field winding terminal wrt ground and in turn it
measures the value of refelcted pulse and claculates the
insulation value.
For testing generator earth fault relay put specific values
of precision resistors across terminals and observe the
values in relay if display is provided, or set the trip
value less than the resistace put for testing , then relay
will issue trip command and this proves relay is heathy.
Gajanan koshatwar manager Power plant
| Is This Answer Correct ? | 41 Yes | 6 No |
Post New Answer View All Answers
why asa method ZPF method is more accurate than ASA method?
What is earth system using on the floater TN-S or TT. Iam not sure and what ICCP
Enlist four components of electrive drives.
oil cooled transformer
what is resver in electrical enginnering with answer
If I want to buy a new Xformer for my plant what are the main parameter will I need to check?
WHat is the general checks required for Dry type transformers
List few applications of d.c series motor?
How many devices can be connected in one zone of FACP
Readings of ER300P Trivector meter
Explain dc generator with its types?
Hi I'm doing my MBA(3rd semester).I applied for the post of ET conducted by BHEL the last year.I cleared the written and lost in personal interview.Again I wrote the exam this time and cleared the written n yet to take the personal interview.Shall I disclose in the interview about my studies.What shall i say if they ask about my change from studies to job
what is the voltage between earth & neutral in 3 phase electrical connection.
While testing LA mast,What are the parameter limits ?
given data are load current & power factor cable core size? plz any one update the calculation formula