What is the formula for calculating Transformer Losses &
Efficiency. I want to compare the Transformer efficiency at
different loading condition.
Answer Posted / kashifhabib
Efficiency = (Output/Input)*100
&
Output (KW)= KVA * Power Factor
Input = Output + Iron losses + Copper losses
Iron losses are due to Primary voltage so remains constant
can be calculated by open circuit test
Copper losses are due to secondary current I*I*R
can be calculated by short circuit test
Exp: Full load copper losses 800 W
1/2 load copper losses will be 200 watts
| Is This Answer Correct ? | 368 Yes | 101 No |
Post New Answer View All Answers
WHY EXCITER PHASE SEQUENCE ARE OPPOSITE THAN STATOR SUPPLY PHASE SEQUENCE IN SYNCHRONOUS MOTOR >
what would happen if reactive power (kvar)is increased (more)or decreased (less)? how much exact reactive power should be maintained? and what should be done for that
Hello sir i m student of gtu .what is idp.
Where voltage are high and current to be interrupted is low the breaker preferred is:
What is the purpose of stand by earth fault protection for transformer ?
How wire size can define in electrical wiring? What is the ratio?
Star Delta Diagram with full description
what is the formula of starting current of 3phase and 1 phase motor???
what may the reason for vector shift in a generator?
The simple way of finding the leakage quantity and % in compressed air distribution system
please suggest some good universities with low cost iam in totally full confusion so please help me my profile gre 283 and ielts 5.5
What determines the thickness of the lamination or stamping?
i have applied for the post of RRB section engineering chennai board please send me previou papers and solved answer. my mail id jagarapusrinivas@gmail.com
Why CBCT rating is 50/1A
What is a single phase autotransformer?