Answer Posted / harsh zala
Yes, We can use control valve without a positioner. The
basic purpose of positioner is to supply required punemetic
air w.r.t 4-20 mA standard signal, you can say for example
3.2 kg/cm2 to 4 kg/cm2. and it also checks for the
appropriate vavle opening(feedback) and stops air supply
going to valve actuator.
Without Positiner we can use control valve,but we must have
i/p converter, which generally converts 4-20 mA signal to
0.2 -1 kg/cm2, so in that case valve will not opearate
fully . but it will opearate upto certain level.
So when positoner got fail and we dont have new one, and if
we require valve to be controlled upto certain level, we
can use i/p converter,
| Is This Answer Correct ? | 20 Yes | 6 No |
Post New Answer View All Answers
what should he know if he is an assitent engineer instrumentation in cement industries of experience of 10 - 15 year.
Im having problems with interfase betwen SPI v7.0 and SPPID v5.05. Previous versions of Intools shoul be fixed with SPPIDproj.ocx file. It was necessary to replace this file with one that allows the connection between different versions of SPPID. It is necessary in the current version to do the same?Thanks
what is the difference between active & reactive power?
please can any one tell me clearly about pid tuning i am confusing about this .how to tune pid easly?
steps for installing orifice plate?
What is motion balance principle?
the pump holds on run indication into the dcs and filed local control panel remote push button condition operaton wrong like when the push button pushing conditions the pump is off and the push button release condition the pump is on totally opposite condition . And control room inside give the stop command into dcs just 1secon relay engage and again normal condition. How can I slove
How to calibrate Magnetic flow Transmitter in Field
what is the advantage of submersible level transmitter compare to ultrasonic level transmitter?
how to do dynolab wind speed sensor loop test, how to simulate value,i have simulate mA 4-20mA but not responding in DCS faceplate, please kindly advice me any one.
What happen if I install my pressure transmitter below the elevation of pipe in natural gas service?
the 3 most common transmitter protocol being in refinery or qatar gas and aramco.
How to Calibrate Vortex Flow transmitter in field
How INtools is useful for routine Instrument maintenance?
How to measure the dust in chimney(spm)?