a 3 phase motor was running with delta connected, suddenly
one phase winding got burnt off, what will be the effect ?
Answer Posted / rvg
delta connected winding, one winding burnt off means, its
open circuited. So the motor will work as open delta system
and run normaly with non uniform torque.
The max. load that can carry will be reduced to 57.7% of
full load.
If the motor is connected through a phase faliure relay,
the relay will trip the total ckt.
| Is This Answer Correct ? | 111 Yes | 3 No |
Post New Answer View All Answers
STATE WORKING OF VACCUM CIRCUIT BRAKER?
mostly the questions were from machines... d.c. machines, transformer, synchronous and induction all theory paper........ few from power system... but the level of paper was easy.....
What is Percentage impedence of a transformer? why it is expressed at a percentage? what is the importance of percentage impedence in case of a transformer?
At what factor resistance r of a conductor depends?
how to avoid electrical shock how capacitor store charges wat are the speed control of induction motors state faradays law flemings left hand rule what is rotary converter wat is transmission and distribution what are the sources of energy abrevation of acb,vcb,sf6,igbt what is output equation of transformer which test copper iron and iron loss are calculated what is eddy current draw a single line diagram (10 marks) draw direct online starter(10 marks)
why ups rating in kva? and why ups are in parellel?.why isolation transformer is used in ups?
What tests should i carry over on a newly rewinded DC Generator with voltage rating of 38 volts and current rating of 350 amps, to certify that the machine is OK?
what is meant by directional earth fault and non directional earth fault? describe both.
What is hipot test procedure?
What are the Full Forms of TVM, MTL, CVT ?
who many types of fire explane with exmple
What is the difference between Static and servo controlled voltage stablizer?
What is the reason behind current flow(20 A) in amain earth cable of an SMDB? Is cuurent flow(45A etc) through a neutral cable acceptable?
hi plz send me reliance placement papers..i.e electrical technical papers that have been asked in reliance test.
Hello everyone, somebody knows what is a "surplice power" ? The hole phrase is: "This rating is appropriate for a generator set paralleled with an infinite bus e.g. a national electrical supply network or grid where the generator set is run at 100% load, 24 hours a day, 365 days a year and any surplice power is exported into the grid" Thanks in advance.