WHAT HAPPEN WHEN CT SECONDARY OPEN DURING LOAD
Answer Posted / imran
In normal power transformers primary current depnds upon
the secondary current ( load on secondary side, as load
increases its secondary current increases and also primary
current increases )
While in CT primary current is independent, if CT secondary
opens secondary current becomes zero while primary current
remains as it is. Both currents counter each other during
normal operation, and if secondary opens so secondary
current becomes zero and due to the primary current ( now
no counter effect present ) its core becomes saturated and
CT may blast.
| Is This Answer Correct ? | 6 Yes | 2 No |
Post New Answer View All Answers
During Starter Panel Com missing I Found The Main Incomer 40Amp MCB 10KA Trip When Motor Change Star To Delta Motor Rating 20HP BUT When We Use Same MCB To Other Motor It Does Not trip Or What Is Necessaries for Star Delta Starter MCB SFU MPCB OR MCCB And What are The Breaking Capacity of MCCB in the Motor above 15HP
What is resonant frequency?
What is the voltage gain or transfer function of amplifier?
In 90 kva alternator that produce the output voltage is 115(p-n),200(p-p) at 1500 rpms means what ampere it produced ?
why Current is lead 90 degree and voltage is lag 90 degree in a capacitor.? why Current is lag 90 degree and voltage is lead 90 degree in an inductor.?
What is formula calculation size cable wire ?
We normally make oil soak pits under Transformers. Oil from soak pit goes to collection pit. We provide granules/pebbles under transformers. My question is weather granules/ pebbles to be filled in soak pit or not? if yes upto what level?
why motor range is available 22kv,30kv,37kv,45kv and so on? why motor range is not available 21kv,24,25,26,27kv and so on?
PLZ EXPLIN ABOUT CLASS PS CLASS CT .WHY THEY R DESINED AND FOR WHAT PURPOSE?WHY OTHER CT CANT BE USED AS PS CLASS CT? EXPLAIN IN SIMPLE LAUNGAGE IF POSSIBLE PLZ GIVE CIRCIT DIAGRAM?EMAIL-RAJ_SINGH_0376@SIFY.COM
An 8 pole, 50 Hz, 3-phase IM is loaded to a poing where pull out torque will occur. The rotor resistance per phase is 0.3 ohm and motor stalls at 650 rpm. The slip when motor stalls is A 1 B 0 C 13.33% D 10.33%
How to control motor gearbox speed and friquency? If length of cable and dia given, how to measure the voltage drop?
give single line diagram of D.G distribution form alternator to main L.T panel?
What are the weight of 800KV DA,DB and DC type tower ?
why we have and use 3 phase not 2 or 4 or other in power system?
how we do Vector group ,magnetic balance and tap changer test in Transformer?