what will happen if the secondary of current transformer
kept open....
Answer Posted / max
as CT is connected in series, the if the sec side kept open
high value of the current on te primary side will saturate
the core which might be irrversible and in addition voltage
level at sec side will be very high resulting saftey issues
Is This Answer Correct ? | 22 Yes | 3 No |
Post New Answer View All Answers
what questions will be asked for 11/33KV licence interview APSEB hyderabad. Can any one share question and answers.
how external lighting design? please give examples?
What is the general power consumption rating of CPU CRT type and Flat type, Monitor,Printer, projector, Scanner?
what is the main difference between power devices and signal devices
Can any answer me ,What will be the range of C.T coil for L&T energy meter EM301 used for 180 kva DG set
what is the formula of starting current of 3phase and 1 phase motor???
What is the formula to calculate a three phase alternator
1) why a dg set shows variation of power factor and load when synchronised with other dgs? 2)Why the load sharing is not become equal in all dgs?. 3)When a dg set will not run on auto start?
What is voltage ratio of a transformer?
What are operating procudures & Safety precautions to be observed while operating OLTC in manual mode ?
what is V.L.F. testing of power cable? do you know the voltage ratings, like for what rating and size of cable what rating of V.L.F. testing is used?
for compensate 315mh inductance ,how many capaciance required?
State the other types of Air Conditioners?
How to Calculate The Neutral Earth flat design calculation for the Synchronised generator (Gen 1-650Kva, Gen 2-725Kva
In hydel power plants, L.A's, S.C's are placed inside the control panel boards. what is the purpose? [already the total body was earthed to ground.]