How can we calculate the fault level of the distribution
system knowing the percentage impedance of transformer &
subsequent equipments.
Answer Posted / jigar shah
suppose transformer (11 KV/433) is of 1000 KVA & %
impedance is 4 .LT side Fault level can be calculated as
below :
KVA = 1.732 X V X I X Cos Phi - PF assumed : 0.95
LT Rated current (I) = (1000 * 1000)/(1.732*433*0.95)
= 1481 A
Fault current on LT side = FLC * 100/(% impedance)
= 1481 * 100/5
= 29.62 KA
| Is This Answer Correct ? | 44 Yes | 54 No |
Post New Answer View All Answers
why on axial hitting up of air blast on hydrogen produced in oil circuit breaker,temperature rises of the core of the arc?
HOW can i REuse the fused MLL LAMPS & GLS LAMPS at our factory
what will be d.g. capacity to cater together for 14hp A.C. load & 3kw lighting load
in dc suppy frequency is zero why? if dc frequency is zero how to exist dc transients and ac transients
Some times to change of DOR of a motor, interchange of R & B is not effected and RYB take same current, but interchange of R&Y is effected ie change the DOR. My doubt is what is the problem in motor and how it is happen.
As an electrical engineer what are the responsibilities which i can hold in TCS?
What is Harmonics how it is produced and what is the method to control the same
What is Long rod insulator and it's applications..? merits over the disc insulator ..?
In Power cable specification what is U0/U and Um.
i m in need of current rating chart of heavy duty pvc/xlpe, cu/al cables. can somebody provide me? if yes, plz send me at ashish_patel111@yahoo.com
during installation time of transformer and alternator which points we have to observed?
my b-tech percentage is 50%. what answer will satisfy the hr ?
what are the possible reaons & remedies if resistance of NGR getting heat up
What are the advantages of a three-phase system over a single-phase system?
how do we calculate length of starting time and repeated starting of a direct online starter?