How can we calculate the fault level of the distribution
system knowing the percentage impedance of transformer &
subsequent equipments.
Answer Posted / jigar shah
suppose transformer (11 KV/433) is of 1000 KVA & %
impedance is 4 .LT side Fault level can be calculated as
below :
KVA = 1.732 X V X I X Cos Phi - PF assumed : 0.95
LT Rated current (I) = (1000 * 1000)/(1.732*433*0.95)
= 1481 A
Fault current on LT side = FLC * 100/(% impedance)
= 1481 * 100/5
= 29.62 KA
| Is This Answer Correct ? | 44 Yes | 54 No |
Post New Answer View All Answers
What is Harmonics how it is produced and what is the method to control the same
If the line voltage is reduced to 75% of its rated value then by what percentage current will reduce ?? 75% 25% 50% no change and why ?
how is the testing of an REF relay? what are the test REF circuit having?
When the relative speed between the magnetic fields of stator and rotor does is zero under steady state operation?
what is meant by class 1 E in electrical power supply?
Determine a suitable number of slors and conductors per slot for the starter 1 winding of a 3 phase, 3300 V. SO Hz 300 rpm alternator. The diameter is 2.3 m
Briefly describe your ideal job?
Pl.brief me about Electrical power distribution system from Main generating station to Industry.What is the use of in between station.
hi,every one, i have to write the search paper on "performance policy optimization" of NGN (next generation networks). i need the material on this topic. can any body help me. please tell me any useful site where the good material is available and name of any reference book. it should be a great help for me.
ht side line to earth voltage
I have been using an 600VA with 0.6 p.f UPS with my desktop which has 450W power supply unit. Can anyone explain how can this happen . Because the output of the UPS is 360W (600*0.6) (<450W)
what is transformor oil gread
Explain marx circuit.
what is doid
How to calculate multiplication factor in kva example 500kva ans pls ?