How can we calculate the fault level of the distribution
system knowing the percentage impedance of transformer &
subsequent equipments.
Answer Posted / jigar shah
suppose transformer (11 KV/433) is of 1000 KVA & %
impedance is 4 .LT side Fault level can be calculated as
below :
KVA = 1.732 X V X I X Cos Phi - PF assumed : 0.95
LT Rated current (I) = (1000 * 1000)/(1.732*433*0.95)
= 1481 A
Fault current on LT side = FLC * 100/(% impedance)
= 1481 * 100/5
= 29.62 KA
| Is This Answer Correct ? | 44 Yes | 54 No |
Post New Answer View All Answers
hi,every one, i have to write the search paper on "performance policy optimization" of NGN (next generation networks). i need the material on this topic. can any body help me. please tell me any useful site where the good material is available and name of any reference book. it should be a great help for me.
In aerodynamic turbines which element is NOT there a.stator b.compressor c. Fuel intake system d.fans
how we sesign the transformer give some specifion regarding design of transformers
Why do we perform an open-circuit test and short-circuit test on the transformer?
What are all present producing cost of Per KWH of various Fuel?
how does an centrifugal and screw type chiller will work. which chiller efficiency is high and why.
How to do stting of vl250 siemens MCCB
what does mean of RCT and STR in diffrential CT?
what is V.L.F. testing of power cable? do you know the voltage ratings, like for what rating and size of cable what rating of V.L.F. testing is used?
what is the k var ratting of 1250kva
types of central Air conditioner plant?
What is the drawback of static coefficients?
what is 30-phase of transformer
What is the formula for calculating the Instantaneous Short Circuit & overcurrent for any breaker
What is the pro & con of having 11kv & 33kv incoming, and what is the adv & disadv. of converting from 11kv to 33kv.